Connecting
4.6 Transmitter power supply, communications and I/Os connection
Connect wires
Note
Additional load resistor
Depending on the internal load of an externally connected device, an additional load resistor
might be required, for the pulse, status and frequency functions to work properly,
1. Remove cap and ferrule from cable gland and slide onto cable.
Wall mount enclosure: Remove blind plug and fit cable gland.
2. Push cable through open gland and cable path.
3. Restore ferrule and tighten cap to lightly hold cable in place.
4. Fold signal cable screen back over outer sheath and ground beneath cable clamp.
In case of shielded cables, use metal cable glands for proper connection.
5. Connect wires to terminals using a screwdriver.
Note
The terminal connector is detachable
For easier access unplug the terminal connector. After connecting the wires, plug the
terminal connector back in.
6. Tighten cable gland.
The numbers in the graphics below refer to table Figure 4-7 Terminals/configuration overview
(Page 45)
If connected as input or output (channels 2 to 4)
Termination example for channel 3
48
Active configuration
-
+
Passive configuration