Delivery And Handling; Transport; Assembly - Nibe F1355 Installer Manual

Ground source heat pump
Hide thumbs Also See for F1355:
Table of Contents

Advertisement

2 Delivery and handling

Transport

F1355 should be transported and stored vertically in a
dry place. While being moved into a building, the heat
pump may be tilted back 45 °.
NOTE
The heat pump is top heavy.
If the cooling modules are pulled out and transported
upright, F1355 can be transported on its back.
NOTE
Ensure that the heat pump cannot fall over
during transport.
TIP
The side panels can be removed for easier in-
stallation in the building.
Lift from the street to the set up location
If the base allows, the simplest thing is to use a pallet
truck to move the F1355 to the set up location.
NOTE
The centre of gravity is offset to one side (see
print on the packaging).
F1355 must be lifted on the heaviest side and can be
moved on a sack truck. Two people are required to lift
F1355.
Lift from the pallet to final positioning
Before lifting, remove the packaging and the load anchor
to the pallet as well as front and side panels.
Before lifting, the heat pump must be separated by
pulling the cooling modules out from the cabinet. See
the service chapter in the operating manual for instruc-
tions about the separation.
Carry the heat pump by the upper cooling module's slide
rails, use gloves.
NOTE
The heat pump must not be moved when only
the lower cooling module has been pulled out.
If the heat pump is not secured in position the
upper cooling module must always be removed
before the lower one can be pulled out.
NIBE F1355
15 - 40 mm
0
R
0
R
30 - 50 mm
Scrapping
For scrapping, remove the product in reverse order.

Assembly

Position F1355 on a fixed foundation that can take the
weight of the heat pump. Use the product's adjustable
feet to obtain a horizontal and stable set-up.
20-55 mm
30 - 50 mm
Because water comes from F1355, the area where the
heating pump is located must be equipped with floor
drainage.
Install with its back to an outside wall, ideally in a room
where noise does not matter, in order to eliminate
noise problems. If this is not possible, avoid placing it
against a wall behind a bedroom or other room where
noise may be a problem.
Wherever the unit is located, walls to sound sensitive
rooms should be fitted with sound insulation.
Route pipes so they are not fixed to an internal wall
that backs on to a bedroom or living room.
Installation area
Leave a free space of 800 mm in front of the product.
Approx. 50 mm free space is required on each side, to
remove the side panels (see image). The panels do not
need to be removed during service. All service on F1355
can be carried out from the front. Leave space between
the heat pump and the wall behind (and any routing of
supply cables and pipes) to reduce the risk of any vibra-
tion being propagated.
*
(50)
* A normal installation needs 300 – 400 mm (any side) for connec-
tion equipment, i.e. level vessel, valves and electrical equipment.
H M flo w 4 9 (5 0 )
°C
H o t w a te r 5 1 °C
-2
0
+ 2
0
1
R
*
(50)
800
Chapter 2 |
Delivery and handling
H o t w a te r 5 1 °C
H M flo w 4 9 (5 0 )
°C
-2
0
+ 2
1
0
R
9