Connecting wiring
Wind the wire around the cable strap once to prevent loose wires as shown in the figure.
Transmission cable specifications
Transmission cables
Shielding wire (2-core)
Type of
cable
CVVS, CPEVS or MVVS
Cable
AWG16 [1.25 mm
diameter
wire (2-core) CVVS, CPEVS or
Specifications are subject to change without notice.
PAC-AH001-1
Fig 7.0.1
ME Remote controller
2
] shielding
AWG 20 -16 (0.5 - 1.25
MVVS
30
Ⓐ Cover
Ⓑ Power Supply Terminal Block
(208, 230 VAC)
Ⓒ M-Net Terminal Block
Ⓓ Terminal Block TB-A
Ⓔ Terminal Block TB-B
Ⓕ Terminal Block TB-C
Ⓖ Terminal Block TB-D
Ⓘ Damper Signal Output (D1,
D2)
Ⓙ MA Controller (1, 2)
Ⓚ Analog Input (B1, B2)
Ⓛ Operation Signal Output
(Ocom, OE, OH, OC, OD)
Ⓜ Heater Signal Output (H1,
H2)
Ⓝ Remote Signal Input (A1, A2)
Ⓞ Error Signal Input (E1, E2)
Ⓟ Float Switch Input (FS1, FS2)
Ⓠ Thermistor, Outlet Air (TH1,
TH2)
Ⓡ Thermistor, Gas Pipe (TH3,
TH4)
Ⓢ Thermistor, Liquid Pipe (TH5,
TH6)
Ⓣ Thermistor, Inlet Air (TH7,
TH8)
Ⓤ LEV 1
Ⓥ LEV 2
cables
Sheathed 2-core cable (unshielded) CVV
2
a
mm
)
MA Remote
controller cables
AWG 22-16 (0.3 -
2
a
1.25 mm
)