Connecting Refrigerant Pipes; Refrigerant Piping Work - Mitsubishi Electric CITY MULTI PAC-AH001-1 Installation Manual

Ahu controller
Hide thumbs Also See for CITY MULTI PAC-AH001-1:
Table of Contents

Advertisement

Available languages

Available languages

6. Connecting refrigerant pipes

6.1 Refrigerant piping work

This piping work must be done in accordance with the installation manuals for the outdoor and LEV Kit
Applications Guide.
• For constraints on pipe length and allowable difference of elevation, refer to the outdoor unit manual.
Cautions on Refrigerant Piping
• Be sure to use non-oxidative brazing for brazing to ensure that no foreign matter or moisture enter into
the pipe.
• Be sure to apply refrigerating machine oil over the flare connection seating surface and tighten the
connection using a double spanner.
• Provide a metal brace to support the refrigerant pipe so that no load is imparted to the indoor unit end
pipe. This metal brace should be provided 20 in [~50 cm] away from the indoor unit's flare connection.
WARNING
When installing and moving the unit, do not charge it with refrigerant other than the
refrigerant specified on the unit.
- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to malfunction
and result in severe damage.
Specifications are subject to change without notice.
PAC-AH001-1
22

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents