Powering External Devices - Notifier RP-1001 Installation Manual

Deluge - preaction control
Table of Contents

Advertisement

Installation Procedure
3RZHULQJ([WHUQDO'HYLFHV
18
www.PDF-Zoo.com
$ODUP5HOD\
One Form-C dry contact alarm relay is provided in the
basic panel for controlling supplementary devices. Con-
tacts are rated 2 amps at 30 VDC and 0.5 amps at 30
VAC (resistive) and are non-silenceable when an alarm
occurs.
7URXEOH5HOD\
One Form-C dry contact trouble relay is provided in the
basic panel for controlling supplementary devices.
It is rated 2 amps at 30 VDC and 0.5 amps at 30 VAC
(resistive) and will silence when the trouble condition is
cleared.
Note: Power connected to these relay contacts must come
from a power-limited supply. Power may be obtained
from TB1 Terminals 1-2, TB1 Terminals 3-4, TB2
Terminals 1-2, or a UL-listed power-limited supply.
CAUTION: Several different sources of power can be connected to this panel.
  
Disconnect all sources of power before servicing. The panel and associated
equipment may be damaged by removing and/or inserting cards, modules, or
interconnecting cables while this unit is energized.
RMS-Regulated Power
24 VDC power for inductive-
type devices such as door
holders can be connected to
TB1 terminals 1 (+) and 2(-).
This output is not suitable for
powering devices requiring
filtered DC power.
%
Four-Wire Smoke Detector Power
24 VDC filtered, resettable power
for four-wire smoke detectors can be
obtained from TB1 Terminals 3(+)
and 4(-).
The combined current draws from the
Resettable and Nonresettable outputs
cannot exceed 200 mA.






+24VU
+24VR
+24VNR
Figure 2.5 Power Terminals

Powering External Devices

Alarm
Trouble
NO NC C
NO NC C
Trouble
Alarm
Figure 2.4 Schematic Representation
of Alarm/Trouble Coils & Contacts
Nonresettable Power
24 VDC filtered, nonresettable
power can be drawn from TB2
Terminals 1 (+) and 2(-).
The combined current draws
from the Resettable and
Nonresettable outputs cannot
exceed 200 mA.
%

RP-1001 15150:F 05/24/2001