Start Procedure

1. Start the blower.
2. Open all the gas cocks.
3. Start the ignition sequence.
4. Verify that flame is present at each burner.
■ If a burner does not light, and the system does not
shut down automatically, then you must close the
main gas cock. An uncontrolled flow of gas can
cause fires and explosions.
■ Do not touch the ignition plug or the ignition wire
when the ignition is on. You will get a shock.
14
DANGER

Stop Procedure

1. Close the following valves:
• The manual gas cock for each burner or zone
• The manual gas cock at the main control valve
• All the manual shut-off valves in the gas line
upstream of the burner gas cock
2. Let the burners cool down. Keep the blower on until the
chamber temperature is less than 1000°F (500°C) and
then stop the blower.
NOTICE
■ Keeping the blower on after the burner is off
protects the burner and the other components
from hot gases that flow back through the burner.
Eclipse Furnnox Burner, V1, Installation Guide 210, 2/14/2011