Table 2
Terminal Description for WEB-C3036EP controller
Terminal Description
1,2
Not used
3, 4
2 wire SYLK bus to connect SYLK modules
5, 7, 8
Universal inputs UI-1 to 3. Software
controlled input type selection supports 10k
Thermistor (type II), Dry Contact, 0-10Vdc,
0-20mA, and Pulse (In-1, -2, -3)
6
COM terminal for UI-1 & UI-2
9
COM terminal for UI-3 & UI-4/AO-1
10, 11,
Universal Inputs/Outputs as UI-4 to 6
13
Analog Outputs: selectable 0-10vDC or 0-
20mA
12
COM terminal for UI-5/AO-2 or UI-6/AO-3
14
Supplies 20V DC
15
Controller input supply voltage 24VAC
16
Supply voltage GND
17
Electrical grounding / Earth
18
24VAC output from controller's power
(terminal 15) for DO devices
19
HOT B. Supplies power to common side of
controller's DO (For DO 5,6)
20
HOT A. supplies power to common side of
controller's DO (DO 1, 2, 3, 4)
22, 25,
GND terminal for DO-1&2, DO-3&4, DO-5&6
28
respectively
21, 23,
DO-1 to DO-4
24, 26
27, 29
DO-5, DO-6

Ethernet Connections

Fig. 5
Ethernet Connections
CIPer controller has a built-in four-port 1Gig Ethernet
switch that supports 10BASE-T (10 Mbps), 100BASE-
TX (100 Mbps), and 1000BASE-T (1000 Mbps)
Ethernet connections. It automatically operates at
1000 Mbps if other devices and cabling support it.
© Honeywell
Table 3
Ethernet Connections
Ethernet
An RJ-45 jack for connection to Ethernet is
RJ-45 jack
on top of the CIPer controller. Pin
designations for the RJ-45 jack are shown.
+ ‒
+
+
1 2 3 4 5 6 7 8
Cable type
Use an approved Category 5e or better
and
Ethernet drop cable with RJ-45 plugs. Use
length
professionally manufactured cables of no
more than 328 feet (100 meters).
Disposal
The product should not be disposed of with other
household waste. Check for the nearest authorized
collection centers or authorized recyclers. The correct
disposal of end-of-life equipment will help prevent
potential negative consequences for the environment
and human health. Do not burn this device.

Conformance statement

This Class B digital apparatus complies with Canadian
ICES-003.
This device complies with Industry Canada
licenseexempt RSS standard(s). Operation is subject to
the following two conditions: (1) this device may not
cause interference, and (2) this device must accept
any interference, including interference that may
cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie
Canada applicables aux appareils radio exempts de
licence. L'exploitation est autorisée aux deux
conditions
suivantes: (1) l'appareil ne doit pas produire de
brouillage, et (2) l'utilisateur de l'appareil doit accepter
tout brouillage radioélectrique subi, même si le
brouillage est susceptible d'en compromettre le
Page 5
Pin Assignment
+
1
Bi-directional pair
A+
2
Bi-directional pair
A-
3
Bi-directional pair
B+
4
Bi-directional pair
C+
5
Bi-directional pair
C-
6
Bi-directional pair
B-
7
Bi-directional pair
D+
8
Bi-directional pair
D-
31-00183-02

Advertisement

loading