NB : Only one phase is shown in these instructions. Make off all three phases
the same way. Use a cable conversion kit for 3-core cables.
EQUIPMENT
Separable tee connector
first male connector
1 Train the cable into the approximate finished
position next to the equipment bushing. Be sure
to allow enough extra length of screen wires
to connect to earth.
2 Mark centre line « M » of the bushing.
3 Remove the outer cable sheath to a point 245 mm
from the centre line « M » of the bushing.
or
cut back
point of
outer
sheath
M
245
applications :
one layer of water sealing
mastic (type MWS)
outer cable
sheath
4 For indoor applications, bend the screen wires back
over the outer sheath and proceed to step no. 5.
For outdoor applications:
- Wrap one layer of water sealing mastic (type MWS)
around the outer sheath, flush with the end (25 mm
minimum width). Completely encircle the cable.
- Bend the screen wires back over the mastic and
along the outer sheath, pressing them into the
mastic.
- Important: screen wires should not touch each
other when pressed into the mastic to prevent water
ingress.
5 Apply a tape marker around the outer sheath 65 mm
from the edge.
6 Cut the cable to a point 200 mm from the outer
sheath.
Page 3 of 14
CUT
HERE
edge of the
outer sheath
For outdoor
65
tape
marker
copper
wires
200