IMPORTANT SAFETY INFORMATION

Read all instructions before installation
WARNING - Risk of Electric Shock.
1. Before installing this luminaire or doing any maintenance, make sure to
turn off the power at the circuit breaker or fuse box.
2. Do not handle energized module with wet hands or when standing on wet
or damp surfaces, or in water.
3. This luminaire must be installed in accordance with the national and
local building codes and electrical wiring codes including wiring methods
and wiring connections. If you are not familiar with these codes and
requirements, consult a qualified electrician.
4. The following are not provided: conduit, cable, fittings, terminal blocks and
wire connectors. Refer to Cree's Requirements for Electrical Installation
Materials sheet provided with luminaire.
5. Luminaire suitable for damp locations.
6. Suitable for suspended ceilings if access above ceiling is provided.
7.
DO NOT install insulation material within 76mm (3in) of any part of
luminaire.
8. Lens portion of luminaire, intended for room side, is suitable for
IP 23 locations. Remainder portion of luminaire is only suitable for
IP 20 locations.
9. When looping-in the Mains supply wiring for connecting multiple
luminaires, DO NOT exceed the 16AMP rating of the luminaire terminal
block
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
The CR Series of recessed troffers is for non-insulated ceiling applications only, using T-Bar ceiling grid.
Designed for use on 220-240V, 50-60 Hz protected circuits (fuse box, circuit breaker). Recommended supply wire into luminaire is 1.5mm
2
2.5mm
stranded or solid, rated 90°C or higher.
Supply wire for branch circuit sized in accordance with National and Local electrical wiring codes rated 90 °C or higher.

TO INSTALL:

1
Junction Box Cover
2
Dimming
connection
(optional)
Junction Box
Power
Connection
1 of 2
Including: 300x1200mm, 600x1200mm, 600x600mm Luminaires
Dimming
connection
(optional)
CR Series Troffers 220-240V
CR14, CR24, CR22 Architectural Troffer
INSTALLATION INSTRUCTIONS
CR14
CR24
CR22

STEP 1:

Unpack the CR troffer from its shipping container.

STEP 2:

Place the CR troffer into the T bar ceiling panel.
Assembly should fit tight and not need fasteners. See
Figure 1.

STEP 3:

Locate electrical junction box. Remove junction
box cover to access the luminaire's power wiring
terminal block. See Figure 2.

STEP 4:

Using a screw driver blade, remove appropriate
wiring knockout from junction box. Connect
customer supplied power conduit to Junction
box using appropriate customer supplied conduit
fittings. See Figure 2.

STEP 5

If luminaire has a dimming option using a screw
driver blade, remove appropriate knockout from
the junction box. Connect customer supplied
dimming conduit to Junction box using appropriate
customer supplied conduit fittings. See Figure 2.

STEP 6:

Install appropriate customer supplied wiring into
conduits and luminaire's junction box.
2
to
LPN000139_D

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CR Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Cree CR Series

  • Page 1 CR Series Troffers 220-240V CR14, CR24, CR22 Architectural Troffer Including: 300x1200mm, 600x1200mm, 600x600mm Luminaires IMPORTANT SAFETY INFORMATION INSTALLATION INSTRUCTIONS Read all instructions before installation WARNING - Risk of Electric Shock. 1. Before installing this luminaire or doing any maintenance, make sure to turn off the power at the circuit breaker or fuse box. CR14 2. Do not handle energized module with wet hands or when standing on wet or damp surfaces, or in water. 3. This luminaire must be installed in accordance with the national and local building codes and electrical wiring codes including wiring methods and wiring connections. If you are not familiar with these codes and...
  • Page 2 GREEN/YELLOW OR GREEN/ UNINSULATED (BARE) EARTH YELLOW © 2014 Cree, Inc. All rights reserved. For informational purposes only. Content is subject to change. See www.cree.com/lighting/products/warranty for warranty and specifications. Cree® and the Cree logo are registered trademarks. www.cree.com/lighting LPN000139_D 2 of 2...

This manual is also suitable for:

Cr14Cr22Cr24

Table of Contents