4. Commissioning
One or more configuration lists have been
created in the PLC or in the INTERBUS module
for logical addressing. These lists contain at
least the following entries:
– the ID codes of all slaves
– the logical addresses of all slaves
– the number of inputs
– the number of outputs
These specifications must be known or ascer-
tained for each bus slave. In order to do this,
proceed in the case of the valve terminals as
follows:
Calculate the number of I/Os per valve
terminal
(see Chapter 2.1, "Calculating the
number of I/Os).
Take into account the four status bits in the
case of valve terminals with inputs.
Ascertain the Ident code and the number of
bits of the process data channel in accord-
ance with the following table.
Assign logical IN and OUT addresses to each
slave.
4-25