VIFB6 - 03/05
9809c
4. Commissioning
One or more configuration lists have been
created in the PLC or in the INTERBUS module
for logical addressing. These lists contain at
least the following entries:
– the ID codes of all slaves
– the logical addresses of all slaves
– the number of inputs
– the number of outputs
These specifications must be known or ascer-
tained for each bus slave. In order to do this,
proceed in the case of the valve terminals as
follows:
•
Calculate the number of I/Os per valve
terminal
(see Chapter 2.1, "Calculating the
number of I/Os).
•
Take into account the four status bits in the
case of valve terminals with inputs.
•
Ascertain the Ident code and the number of
bits of the process data channel in accord-
ance with the following table.
•
Assign logical IN and OUT addresses to each
slave.
4-25