Parameter Description

Main Menu - Smart Logic - Group 13

13-** Prog. Features Prog. Features
Smart Logic Control (SLC) is essentially a sequence of user defined actions (see par.13-52
tion
[x]) executed by the SLC when the associated user defined
evaluated as TRUE by the SLC. Events and
event
that when
[0] is fulfilled (attains the value TRUE),
[1] will be evaluated and if evaluated TRUE,
event
at any time. If an
is evaluated as FALSE, nothing happens (in the SLC) during the current scan interval and
events
no other
will be evaluated. This means that when the SLC starts, it evaluates
each scan interval. Only when
event
[1]. It is possible to program from 1 to 20
event
action
When the last
/
illustration shows an example with three event / actions:
Starting and stopping the SLC:
Starting and stopping the SLC can be done by selecting
SLC always starts in state 0 (where it evaluates
13-01
Start
Event) is evaluated as TRUE (provided that
Stop Event
SLC stops when the
and starts programming from scratch.
13-0* SLC Settings
Use the SLC settings to activate, deactivate and reset the Smart Logic Control.
13-00 SL Controller Mode
Option:
[0] *
Off
[1]
On
13-01 Start Event
Option:
[0] *
False
[1]
True
136
actions
are each numbered and linked together in pairs. This means
action
[1] will be executed and so on. Only one
event
[0] is evaluated TRUE, will the SLC execute
events
has been executed, the sequence starts over again from
event
[0]). The SLC starts when the Start Event (defined in par.
(par.13-02
Stop
Event) is TRUE. par.13-03
Function:
Disables the Smart Logic Controller.
Enables the Smart Logic Controller.
Function:
Select the boolean (TRUE or FALSE) input to activate Smart Logic Con-
trol.
Enters the fixed value of FALSE in the logic rule.
Enters the fixed value TRUE in the logic rule.
event
(see par.13-51
action
[0] is executed. After this, the conditions of
action
actions
and
.
On
Off
[1] or
[0] in par.13-00
On
[1] is selected in par.13-00
Reset SLC
SL Controller Ac-
SL Controller Event
[x]) is
event
event
will be evaluated
event
event
[0] (and only
[0])
[0] and start evaluating
event
action
[0] /
[0]. The
SL Controller
Mode. The
SL Controller
Mode). The
resets all SLC parameters
TR200 Programming Guide