The dehumidifier maintenance and inspection works should be performed in accordance with a fixed schedule. Only original spare parts should be used. It is required to receive a written approval from «DanVex Оу.» or from its local representative for any changes or modifications of the dehumidifier. www.danvex.fi...
Purpose DanVex AD-550 (in short AD-550) is designed for efficient air dehumidification with the air humidity up to 100%, at the temperature from –20ºС to +40ºС with minimum energy consumption. It can be used either as an independent unit for installation inside and outside of premises where air humidity control is required or along with an air treatment system.
Note: defaulted value is “080" (80%), and the return difference is “005" (5%), it means that: while the ambient RH levels higher than 80%, it will works; while the ambient RH level is lower than 75% it will pause. 3) Indicator of heater temperature 4) Timer - clockmeter, showing the working time of dehumidifier www.danvex.fi...
Pic.1. Dehumidifier air flows diagram Dimensions and weight Table 1 Insignificant design changes are possible! Dehumidified Height Reactivation Moist air Length Depth Dry air Weight 65 kg ø 100 mm ø 100 mm 755mm 415mm 860mm ø 200 mm ø 200 mm www.danvex.fi...
Installation Installation and the covered area AD-550 dehumidifier is designed for indoor installation. It should be positioned upright on an even surface. It is recommended to fix the dehumidifier. It is required to leave some free space (1000 mm) in front and above the dehumidifier for filters, fans and rotor maintenance and inspection.
Technical data of AD-550 о Moisture output 0,6 kg/hour (at +20 C and RH 60%) Table 2 Parameter Unit Value Dehumidified air* m /hour Rated air consumption Reactivation air* m /hour Rated air consumption Electric power and rated current Total power...
Upon delivery it is required to check the dehumidifier for transportation damages. The dehumidifier should be protected from rain and snow. The dehumidifier should always be in upright condition. It is not allowed to put heavy objects on the dehumidifier. www.danvex.fi...
The warranty does not cover wearable parts such as filters. The warranty covers the defects in workmanship and materials. During the warranty period DanVex repairs and replaces the part having a defect of material or an manufacturing error. DanVex completely fulfills its warranty obligations when it supplies the Customer a repaired or a spare part.
Need help?
Do you have a question about the AD-550 and is the answer not in the manual?
Questions and answers