3.3 Technical data

TROVIS 5757-3 Electric Actuator with Process Controller
Connection to valve
Rated travel
Transit time for rated travel
Thrust
Power supply
Power consumption
Manual override
Permissible temperatures
Ambient
Storage
Degree of protection
Class of protection
Electromagnetic compatibility
Mounting position
Compliance
Weight
Inputs and outputs
Binary input BI1
2)
Binary input BI2
2)
Version with switching output (firmware version 2.0x/2.1x)
Switching output
Accessories
Temperature sensor
Water flow sensor
Flow switch
Control input
The permissible medium temperature depends on the valve on which the electric actuator with pro-
1)
cess controller is mounted. The limits in the valve documentation apply.
Recommendation: use devices with gold contacts when using relays.
2)
EB 5757 EN
Force-locking
6 mm
20 s
300 N
230 V (±10 %)/50 Hz
Approx. 3 VA
Yes
1)
0 to 50 °C
–20 to +70 °C
IP 42 according to EN 60529
II according to EN 61140
According to EN 61000-6-2, EN 61000-6-3 and
EN 61326
Any position except suspended
Approx. 0.7 kg
Set point switchover (W1 and W2, see section 10.2)
Flow switch
230 V, 50 Hz, max. 1 A
Pt 1000, fast response: –50 to 150 °C
530 pulses/l
Floating contact
0/4 to 20 mA
Design and principle of operation
·