Siemens SINAMIC G130 Operating Instructions Manual page 34

Braking module / braking resistor
Table of Contents

Advertisement

Connection
4.2 Connecting the Braking Module
Recommended connection for terminal strip X21
The signals of terminal strip X21 can be freely used corresponding to the line-side
requirements.
In connection with the system components used and the default settings of the command
sources during commissioning, the following recommendations for the wiring of the signals
apply.
● X21:2 to CU X132:14 (mass)
● X21:3 on CU X132:9 (DO12 = acknowledge fault)
● X21:5 on CU X132:1 (DI4 = external fault 3)
● X21:6 on CU X132:13 (DO15 = P24V)
Parameterization
Table 4- 4
Parameterization
Parameters
p1240
Vdc controller or Vdc monitoring
configuration
p2108
Ext. fault_3
p3111
BI: External fault 3 enable
p0728.12
Sets CU input or output:
DI/DO 12 (X132.9)
p0742
BI: CU signal source for terminal
DI/DO 12 (X132.9)
Note
Fault acknowledged with r2138.7 for the recommended wiring
If, during operation, an "Acknowledge fault" signal is initiated via terminal X21.3 in the
braking chopper, without there being a fault in the Braking Module, then this initiates an
external fault 3.
You can prevent this response by applying the following measures:
• Link the "Acknowledge fault" signal with status bit 3 "Fault active" of status word ZSW1
(r2139.3).
• If a fault is not active, then do not initiate an "Acknowledge fault" signal.
32
Sink
Description
Vector
Vector
Vector
CU
CU
DO
Parameters
0
Inhibit Vdc ctrl
r0722.4
DI 4 (X132.1)
r0899.2
Operation enabled
1
Sets DI/DO12 as output
(corresponds to the default setting
after commissioning and selection
of p0700)
r2138.7
Acknowledges the fault
(corresponds to the default setting
after commissioning and selection
of p0700)
Operating Instructions, 11/2017, A5E00331454A
Source
Description
Braking Module / braking resistor
DO
CU
Vector
Vector