FORM 121.00-EG1
ISSUE DATE: 5/31/2012
Floor Concealed (JFM Type)
Indoor unit (E)
MODEL No.
Power source
Controller P.C.B. Ass'y
Fan (Number...diameter)
Fan motor
Model...Nominal output
Power source
No. of pole...r.p.m. (230V, High)
Coil resistance
(Ambient temperature 20°C)
Safety device
Operating temperature
1
Run capacitor
Electronic expansion valve
Coil
2
Coil resistance (at 20°C)
Valve body
Heat exchanger
Coil
3
Rows...fi n pitch
Face area
4
5
6
7
8
JOHNSON CONTROLS
in (mm)
W
rpm
BRN – WHT : 67.62
WHT – VLT : 18.47
VLT
– ORG : 10.10
Open °F(°C)
Close °F(°C)
VAC, μF
ORG – GRY : 46
RED – GRY : 46
in (mm)
2
2
ft
(m
)
JFMHX1862N
208 - 230 V / 1ø / 60 Hz
CR-UHX0762 (Microprocessor)
Centrifugal (2...ø6-1/32 (ø153))
KFG4Q-61C6P...30 W
208 - 230 V / single-phase / 60 Hz
4P... 1,066
ORG – YEL : 17.36
YEL – PNK :
266 ± 9 (130 ± 5)
181 ± 9 (115 ± 5)
440 VAC, 2.0 μF
UKV-U030E
YEL – GRY : 46
BLK – GRY : 46
UKV-25D32
Aluminium plate fin / Copper tube
3...5/64 (2.0)
1.8 (0.167)
5.18
150
Need help?