Johnson Controls JX Series Engineering Manual page 150

Mini 2-way variable refrigerant flow vrf system, r410a
Table of Contents

Advertisement

FORM 121.00-EG1
ISSUE DATE: 5/31/2012
Floor Concealed (JFM Type)
Indoor unit (E)
MODEL No.
Power source
Controller P.C.B. Ass'y
Fan (Number...diameter)
Fan motor
Model...Nominal output
Power source
No. of pole...r.p.m. (230V, High)
Coil resistance
(Ambient temperature 20°C)
Safety device
Operating temperature
1
Run capacitor
Electronic expansion valve
Coil
2
Coil resistance (at 20°C)
Valve body
Heat exchanger
Coil
3
Rows...fi n pitch
Face area
4
5
6
7
8
JOHNSON CONTROLS
in (mm)
W
rpm
BRN – WHT : 67.62
Ÿ
WHT – VLT : 18.47
VLT
– ORG : 10.10
Open °F(°C)
Close °F(°C)
VAC, μF
ORG – GRY : 46
Ÿ
RED – GRY : 46
in (mm)
2
2
ft
(m
)
JFMHX1862N
208 - 230 V / 1ø / 60 Hz
CR-UHX0762 (Microprocessor)
Centrifugal (2...ø6-1/32 (ø153))
KFG4Q-61C6P...30 W
208 - 230 V / single-phase / 60 Hz
4P... 1,066
ORG – YEL : 17.36
YEL – PNK :
266 ± 9 (130 ± 5)
181 ± 9 (115 ± 5)
440 VAC, 2.0 μF
UKV-U030E
YEL – GRY : 46
BLK – GRY : 46
UKV-25D32
Aluminium plate fin / Copper tube
3...5/64 (2.0)
1.8 (0.167)
5.18
150

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the JX Series and is the answer not in the manual?

Table of Contents