MINI 2-WAY VARIABLE REFRIGERANT FLOW (VRF) SYSTEM ENGINEERING GUIDE New Release Form 121.00-EG1 (512) MINI 2-WAY VARIABLE REFRIGERANT FLOW (VRF) SYSTEM Issue Date: May 25, 2012...
Page 2
ASHRAE 15 ASHRAE 34 The refrigerant (R410A), which is used in the aircon- ditioner, is safe, without the toxicity or combustibil- JOHNSON CONTROLS...
Page 3
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 INDOOR UNIT NOMENCLATURE UMHX SERIES CAPACITY SLIM CONCEALED DUCT TYPE JOHNSON CONTROLS OUTDOOR UNIT NOMENCLATURE SERIES CAPACITY SALT-AIR DAMAGE RESISTANT 2-WAY FLOW MINI JOHNSON CONTROLS OUTDOOR UNITS CLASS JCHX Variable Refrigerant Flow JCHX03652N JCHX05252N System...
7. INDOOR UNIT WIRING DIAGRAMS ........................171 8. CAPACITY RATIO OF OUTDOOR UNITS .......................196 9. COOLING CAPACITY OF INDOOR UNITS .....................204 Note: 1. All data herein is subject to change without notice. 2. Drawings and performance data should not be used for submittal purposes JOHNSON CONTROLS...
Johnson Controls. You get the freedom to create mediate response to changes in zone loads. With wired comfortable, efficient buildings, without being limited controls, wireless controls and a network portal that by ductwork runs.
Page 6
JOHNSON CONTROLS Mini 2-WAY VARIABLE REFRIGERANT FLOW SYSTEM BENEFITS units have a modular design and compact footprint, choosing a Johnson Controls VRF system means easy Johnson Controls Mini 2-way Variable Refrigerant installation and commissioning. With multiple unit Flow (VRF) systems are easy to select with flexibility connectivity, up to 9 indoor units can be connected to built in to the unit choices.
Page 7
• Network portal that supports BACnet , LON- ® • 208/230 volt — single-phase power supply WORKS and Johnson Controls N2 protocols. ® • Ceiling, wall and floor mounted models available • Standard operation uses return air sensor, but can • Concealed, semi-concealed and exposed models be configured to use the sensor in the controller.
Page 8
• Bottom discharge – should be mounted at least 5’ above the floor and 12” from ceiling • Wireless remote ready – comes with built-in wire- less receiver • Anti-mold washable filter (not MERV rated) • 3-speed AC motor (not ECM) • Condensate pump not included LD16391 JKHX Series - High Wall Mounted Indoor Unit JOHNSON CONTROLS...
Page 9
• Pipes can be connected to either side of the unit from the bottom or rear • Wired controller can be mounted in the unit. • Condensate pump not included LD16393 JAHX 1 Way Air Discharge - Semi-Concealed Cassette LD16394 JFHX - Vertical Floor-Mounted Exposed JOHNSON CONTROLS...
Page 10
• This unit has a draw-through coil – a P-trap will cal box be required for the condensate • 0.16 in. w.g. static pressure enables ductwork to be fitted • Condensate pump built in LD16398 LD16400 JUMHX - Horizontal Concealed Slim JDHX - High-Static Horizontal Concealed JOHNSON CONTROLS...
Page 11
• 7 Day Timer, 6 time periods per day that must be mounted in the field • Temperature set-back • Systems diagnostics capability (with connector cable) • Built in remote temperature sensor LD16497 Wireless Remote Control JOHNSON CONTROLS...
Page 12
• Cannot be used for setback – addition of the schedule timer only allows on/off control • Diagnostic history of system past & present • Maximum installation of two System Controls • Requires separate power supply LD16405 LD16407 JSHA-KC64AGN - System Controller JOHNSON CONTROLS...
Page 13
® ® • Only way to control a VRF system with BAS • This allows communication between the propri- etary VRF controls network and the BMS • Field labor is required to add this to the BMS LD16496 JOHNSON CONTROLS...
JDHX4852N Ceiling-Mounted Type (JT Type) JTHX1252N JTHX1852N JTHX2452N Wall-Mounted Type (JK Type) JKHX0752N JKHX0952N JKHX1252N JKHX1862N JKHX2452N Floor-Standing Type (JF Type) JFHX0762N JFHX0962N JFHX1262N JFHX1562N JFHX1862N JFHX2462N Concealed-Floor Standing Type (JFM Type) JFMHX0762N JFMHX0962N JFMHX1262N JFMHX1562N JFMHX1862N JFMHX2462N JOHNSON CONTROLS...
Page 15
Outdoor discharge Unit 96,000 (28.1)96/ 3-29/32 108,000 (31.6) 25/32 1-13/32 2-3/8 4-11/32 2-3/8 5-1/8 JCHX03652/05252 JCHX03652N/05252N JCHXR03652/05252* JCHXR03652N/05252N* * Outdoor unit model name beginning with letters “JCHXR” Refer to the Section 1. Salt-Air Damage Resistant Specifications”. JOHNSON CONTROLS...
Page 16
(both sides) ( 80 m) Notes: 1 Consult us before introducing a salt-air damage resistant model as it requires a special treatment. 2 The specifications are subject to change without notice for development. 3 Contact us for the delivery schedule. JOHNSON CONTROLS...
* Full-load conditions at Indoor / Outdoor capacity ratio 100% Cooling : Indoor air temperature 89°F DB / 73°F WB ; Outdoor air temperature 109°F DB / 78°F WB Outdoor unit model name beginning with letters "JCHXR" Refer to the Section 1 "Salt-Ait Damage Resistant Specifications". JOHNSON CONTROLS...
Page 18
* Full-load conditions at Indoor / Outdoor capacity ratio 100% Cooling : Indoor air temperature 89°F DB / 73°F WB ; Outdoor air temperature 109°F DB / 78°F WB Outdoor unit model name beginning with letters "JCHXR" Refer to the Section 1 "Salt-Ait Damage Resistant Specifications". JOHNSON CONTROLS...
Page 19
Aluminum plate fin / Copper tube Rows...fin pitch in. (mm) 3 ... 7/128 (1.4) Face area 11.7 (1.08) DATA SUBJECT TO CHANGE WITHOUT NOTICE * Outdoor unit model name beginning with letters “JCHXR” Refer to the Section 1 “2. Salt-Air Damage Resistant Specifications”. JOHNSON CONTROLS...
Page 20
Aluminum plate fin / Copper tube Rows...fin pitch in. (mm) 3 ... 7/128 (1.4) Face area 11.7 (1.08) DATA SUBJECT TO CHANGE WITHOUT NOTICE * Outdoor unit model name beginning with letters “JCHXR” Refer to the Section 1 “2. Salt-Air Damage Resistant Specifications”. JOHNSON CONTROLS...
Page 21
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 1-3. Dimensional Data JCHX03652N, JCHXR03652N JCHX05252N, JCHXR05252N JOHNSON CONTROLS...
Page 23
1000 2000 4000 8000 Frequency at center of sound pressure band (Hz) NOTE 1. dBA = A – weighted sound power level (A – scale according to IEC) 2. Reference acoustic intensity 0 dB = 10 –13 W/ft JOHNSON CONTROLS...
Page 24
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 JCHX05252N, JCHXR05252N Model JCHX05252N, JCHXR05252N Sound Power 68 dB (A) Level Cooling Condition NC ‒ 70 NC ‒ 60 NC ‒ 50 NC ‒ 40 NC ‒ 30 NC ‒ 20 1000 2000 4000 8000 Frequency at center of sound pressure band (Hz) NOTE 1. dBA = A ‒ weighted sound power level (A ‒ scale according to IEC) 2. Reference acoustic intensity 0 dB =10 W/ft ‒13 JOHNSON CONTROLS...
Page 25
NC – 50 NC – 40 NC – 30 Approximate minimum audible limit for continuous NC – 20 noise 1000 2000 4000 8000 Overall Frequency at center of sound pressure band (Hz) * 0 dB = 0.0002 µbar JOHNSON CONTROLS...
Page 26
NC – 50 NC – 40 NC – 30 Approximate minimum audible limit for continuous NC – 20 noise 1000 2000 4000 8000 Overall Frequency at center of sound pressure band (Hz) * 0 dB = 0.0002 µbar JOHNSON CONTROLS...
8.1 (0.228) 3.8 (0.104) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 28
8.1 (0.228) 3.8 (0.104) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 29
8.1 (0.228) 3.8 (0.104) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 30
9.9 (0.279) 3.8 (0.104) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 31
4.6 (0.13) 1.7 (0.047) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 32
4.6 (0.13) 1.7 (0.047) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 33
MP24ZN Coil resistance (at 77°F) 380 ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 34
MP24ZN Coil resistance (at 77°F) 380 ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 35
MP24ZN Coil resistance (at 77°F) 380 ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 36
MP24ZN Coil resistance (at 77°F) 380 ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 37
MP24ZN-12V Coil resistance (at 77°F) 380 ± 7% / phase Drain pump PLD-12230ST-2 Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 38
MP24ZN-12V Coil resistance (at 77°F) 380 ± 7% / phase Drain pump PLD-12230ST-2 Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 5. 4-Way Air Discharge (Mini) Semi-concealed Type (JX, JXM Types) 4-Way Air Discharge Ceiling Semi-Concealed, Standard and Mini (JX, JXM Types) Indoor unit: JXHX3652N JOHNSON CONTROLS...
Page 41
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 4-Way Air Discharge Ceiling Semi-Concealed, Standard and Mini (JX, JXM Types) Indoor unit: JXMHX1252N/JXMHX1852N JOHNSON CONTROLS...
Page 42
STRONG 41 dB(A) WEAK 33 dB(A) CONDITION 4.9 ft directly below unit NC-50 NC-40 NC-30 Approximate minimum audible NC-20 limit for continuous noise 125 250 1000 2000 4000 8000 Overall Frequency at center of sound pressure band (Hz) JOHNSON CONTROLS...
Page 43
0.98 ft/s 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) Cooling : Distribution of temperature (Strong wind : Discharge angle approx.30 ) (Room temperature approx.80°F) 68°F 71°F 75°F 78°F 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
Page 44
0.98 ft/s 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) Cooling : Distribution of temperature (Strong wind : Discharge angle approx.30 ) (Room temperature approx.80°F) 68°F 71°F 75°F 78°F 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
Page 45
16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) Cooling : Distribution of temperature (Strong wind : Discharge angle approx.30 ) (Room temperature approx.80°F) 68°F 71°F 75°F 78°F 16.4 13.1 9.8J 13.1 16.4 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
Page 46
0.98 ft/s 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) Cooling : Distribution of temperature (Strong wind : Discharge angle approx.30 ) (Room temperature approx.80°F) 68°F 71°F 75°F 78°F 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
Page 47
0.98 ft/s 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) Cooling : Distribution of temperature (Strong wind : Discharge angle approx.30 ) (Room temperature approx.80°F) 68°F 71°F 75°F 78°F 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
6.0 (0.170) 2.2 (0.062) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 49
6.0 (0.170) 2.2 (0.062) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 50
6.0 (0.170) 2.2 (0.062) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 51
MP24ZN Coil resistance (at 77°F) 380 ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 52
MP24ZN Coil resistance (at 77°F) 380 ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 53
MP24ZN Coil resistance (at 77°F) 380 ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 54
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 1-Way Air Discharge Ceiling Semi-Concealed (JA Type) Dimensional Data Indoor unit: 7, 9, 12 Type JOHNSON CONTROLS...
Page 55
: JAHX1252N MODEL MODEL JAHX0952N SOUND LEVEL : HIGH 36 dB(A) / LOW 31 dB(A) SOUND LEVEL : HIGH 33 dB(A) / LOW 29 dB(A) CONDITION : Under the unit 4.9 ft CONDITION : Under the unit 4.9 ft JOHNSON CONTROLS...
Shipping volume 8.8 (0.250) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 58
Shipping volume 8.8 (0.250) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 59
Shipping volume 8.8 (0.250) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 60
Shipping volume 8.8 (0.250) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 61
Shipping volume 11.8 (0.334) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 62
Shipping volume 11.8 (0.334) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 63
Shipping volume 16.5 (0.468) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 64
Shipping volume 16.5 (0.468) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 65
Shipping volume 16.5 (0.468) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 66
5.97 (0.169) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 67
5.97 (0.169) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 68
5.97 (0.169) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 69
5.97 (0.169) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 70
5.97 (0.169) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 71
Rows...fi n pitch in. (mm) 2...1 / 16 (1.5) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 72
Rows...fi n pitch in. (mm) 2...1 / 16 (1.5) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 73
Rows...fi n pitch in. (mm) 2...1 / 16 (1.5) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 74
Rows...fi n pitch in. (mm) 3...1 / 16 (1.5) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 75
Rows...fi n pitch in. (mm) 3...1 / 16 (1.5) Face area 2.0 (0.186) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 76
Rows...fi n pitch in. (mm) 3...1 / 16 (1.5) Face area 2.0 (0.186) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 77
Rows...fi n pitch in. (mm) 3...5 / 64 (2.0) Face area 3.3 (0.307) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 78
Rows...fi n pitch in. (mm) 3...5 / 64 (2.0) Face area 3.3 (0.307) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 79
Rows...fi n pitch in. (mm) 3...5 / 64 (2.0) Face area 3.3 (0.307) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 80
(mm) 3...1/16 (1.4) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC 230 V, 60 Hz, 10.8 W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 81
(mm) 3...1/16 (1.4) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC 230 V, 60 Hz, 10.8 W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 82
(mm) 3...1/16 (1.4) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC 230 V, 60 Hz, 10.8 W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 83
(mm) 3...1/16 (1.4) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC 230 V, 60 Hz, 10.8 W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 84
(mm) 3...1/16 (1.4) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC 230 V, 60 Hz, 10.8 W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
Page 85
Bottom drain port (O.D. 1-1/32") Suspension lug Power supply outlet (ø7/8") Fresh air intake port (ø5-29/32") Flange for the flexible air outlet duct (ø7-7/8") Tube cover Electrical component box Flange for the air intake duct Inter-unit control wiring JOHNSON CONTROLS...
Page 86
Bottom drain port (O.D. 1-1/32") Suspension lug Power supply outlet (ø7/8") Fresh air intake port (ø5-29/32") Flange for the flexible air outlet duct (ø7-7/8") Tube cover Electrical component box Flange for the air intake duct (Field supply) Inter-unit control wiring JOHNSON CONTROLS...
Page 87
Suspension lug 7-9/32 Power supply outlet (ø7/8") Fresh air intake port (ø5-29/32") Flange for the flexible air outlet duct (ø7-7/8") Tube cover Electrical component box Flange for the air intake duct (Option or field supply) Inter-unit control wiring JOHNSON CONTROLS...
Page 88
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Slim Concealed Duct, Standard and Slim (JU, JUM Type) Indoor unit : JUMHX0762N/JUMHX0962N/JUMHX1262N/JUMHX1562N/JUMHX1862N Indoor unit : JUMHX0762N/JUMHX0962N/JUMHX1262N/JUMHX1562N/JUMHX1862N Unit: in. JOHNSON CONTROLS...
Page 90
Under the unit 4.9 ft. SOURCE : 208 - 230 V, Single-phase, 60 Hz NC-50 NC-40 NC-30 APPROXIMATE NC-20 THRESHOLD OF HEARING FOR CONTINUOUS NOISE 125 250 500 1000 2000 4000 8000 Frequency at center of sound pressure band (Hz) JOHNSON CONTROLS...
Page 91
To evaluate the noise level, the maximum value of the measured sound pressure level is used. Read the value at each frequency level (on horizontal axis, center of the sound pressure band) from 63 Hz to 8000 Hz, and select the corresponding maximum value indicated on the vertical axis. JOHNSON CONTROLS...
Page 92
To evaluate the noise level, the maximum value of the measured sound pressure level is used. Read the value at each frequency level (on horizontal axis, center of the sound pressure band) from 63 Hz to 8000 Hz, and select the corresponding maximum value indicated on the vertical axis. JOHNSON CONTROLS JOHNSON CONTROLS...
Page 93
(Connected booster cable) 1059 1059 1413 1413 1059 Air Flow Volume (CFM) Air Flow Volume (CFM) Air Flow Volume (CFM) Fig. 7-2 Fig. 4-2 NOTE HT : Using the booster cable H : At shipment JOHNSON CONTROLS 4 - 83...
Page 95
141 (64) Shipping volume 14.8(0.420) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 96
Shipping volume 14.8(0.420) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS JOHNSON CONTROLS...
Page 97
Coil resistance (at 68°F) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-30D33 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 4...5 / 64 (2.0) Face area 3.02 (0.281) JOHNSON CONTROLS...
Page 98
Coil resistance (at 68°F) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-30D33 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 4...5 / 64 (2.0) Face area 3.02 (0.281) JOHNSON CONTROLS...
Page 99
5. Concealed Duct High-Static Pressure Type (D Type) Concealed Duct High Static Pressure (JD Type) Dimensional Data Indoor unit : 36, 48 Type 12-13/64 2-5/32 2-5/32 3-15/16 3-15/16 1-31/32 2-5/32 11-13/16 3-5/32 11-27/64 5-1/8 (Suspension bolt pitch) 3-15/16 3-15/16 3-55/64 1-11/32 JOHNSON CONTROLS...
Page 100
To evaluate the noise level, the maximum value of the measured sound pressure level is used. Read the value at each fre- quency level (on horizontal axis, center of the sound pressure band) from 63 Hz to 8000 Hz, and select the corresponding maximum value indicated on the vertical axis. JOHNSON CONTROLS...
Shipping volume 7.6 (0.215) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 103
Shipping volume 7.6 (0.215) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 104
Shipping volume 9.7 (0.274) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 105
Coil resistance (at 68°F) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fi n / Copper tube Rows...fi n pitch in. (mm) 3...7/128 (1.4) Face area 1.66 (0.154) JOHNSON CONTROLS...
Page 106
Coil resistance (at 68°F) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fi n / Copper tube Rows...fi n pitch in. (mm) 3...7/128 (1.4) Face area 1.66 (0.154) JOHNSON CONTROLS...
Page 107
Coil resistance (at 68°F) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fi n / Copper tube Rows...fi n pitch in. (mm) 3...7/128 (1.4) Face area 2.39 (0.222) JOHNSON CONTROLS...
Page 108
Left side Right side 8-1/2 2-61/64 3-13/16 (Liquid tubing 9/64 Gas tubing) Liquid 2-23/64 tubing Gas tubing 3-5/16 6-11/32 9-7/8 5-3/4 9-7/8 Left drain position Right drain position Closed with rubber stopper at time of shipment. Unit: in. JOHNSON CONTROLS...
Page 109
CONDITION 3.3 ft from front of outlet at height of 4.9 ft NC-50 NC-40 NC-30 Approximate minimum audible NC-20 limit for continuous noise 125 250 1000 2000 4000 8000 Overall Frequency at center of sound pressure band (Hz) JOHNSON CONTROLS...
Page 110
Cooling : Distribution of temperature (Strong wind : Discharge angle approx. -7 ) (Room temperature approx.80 F) 68 F 71 F 75 F 78 F 13.1 13.1 16.4 19.7 23.0 26.2 29.5 32.8 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
Page 111
Cooling : Distribution of temperature (Strong wind : Discharge angle approx. -7 ) (Room temperature approx.80 F) 68 F 71 F 75 F 78 F 13.1 13.1 16.4 19.7 23.0 26.2 29.5 32.8 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
Shipping volume 3.4 (0.096) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 113
Shipping volume 3.4 (0.096) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 114
Shipping volume 3.4 (0.096) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 115
Shipping volume 4.9 (0.139) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 116
Shipping volume 4.9 (0.139) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 117
Coil resistance (at 68°F) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 2...7 / 128 (1.3) Face area 2.06 (0.191) JOHNSON CONTROLS...
Page 118
Coil resistance (at 68°F) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 2...7 / 128 (1.3) Face area 2.06 (0.191) JOHNSON CONTROLS...
Page 119
Coil resistance (at 68°F) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 2...7 / 128 (1.3) Face area 2.06 (0.191) JOHNSON CONTROLS...
Page 120
Coil resistance (at 68°F) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 2...1/16 (1.4) Face area 3.54 (0.329) JOHNSON CONTROLS JOHNSON CONTROLS...
Page 121
Coil resistance (at 68°F) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 2...1/16 (1.4) Face area 3.54 (0.329) JOHNSON CONTROLS...
Page 122
18, 19, 24 type 44-7/8 Drain hose VP13 (length: Approx. 17-23/32”) ø3/8” ø9.52 Drain and wiring port ø5/8” ø ø3/8” ø Gas tube 15.88) (length: Approx. 19-11/16”) Liquid tube 9.52) (length: Approx. 22-7/16”) unit : in. JOHNSON CONTROLS 4 - 114...
Page 123
Overall Overall 125 250 1000 2000 4000 8000 125 250 1000 2000 4000 8000 Frequency at center of sound pressure band (Hz) Frequency at center of sound pressure band (Hz) JOHNSON CONTROLS...
Page 124
(Strong / Outlet Angle=60 ) 91 F 4.9 ft/s 86 F 3.9 ft/s 75 F 80 F 2.9 ft/s 0.98 ft/s 2.0 ft/s 0.98 ft/s 13.1 16.4 13.1 16.4 Horizontal air flow distance (ft.) Horizontal air flow distance (ft.) JOHNSON CONTROLS...
2.70 (0.251) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 126
2.70 (0.251) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 127
2.70 (0.251) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 128
3.43 (0.319) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 129
3.43 (0.319) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 130
3.43 (0.319) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 131
Coil resistance (at 20°C) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-18D31 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.10 (0.102) JOHNSON CONTROLS...
Page 132
Coil resistance (at 20°C) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-18D31 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.10 (0.102) JOHNSON CONTROLS...
Page 133
Coil resistance (at 20°C) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-18D31 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.10 (0.102) JOHNSON CONTROLS...
Page 134
Coil resistance (at 20°C) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.8 (0.167) JOHNSON CONTROLS...
Page 135
Coil resistance (at 20°C) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.8 (0.167) JOHNSON CONTROLS...
Page 136
Coil resistance (at 20°C) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.8 (0.167) JOHNSON CONTROLS...
Page 137
4-ø15/32" hole (For fastening the indoor unit to the floor by screws.) Air filter Refrigerant connection outlet (liquid tube) Refrigerant connection outlet (gas tube) Level adjusting bolt Drain outlet Power supply outlet (ø7/8) Refrigerant tubing outlet (downward, rear) Location for mounting the remote controller JOHNSON CONTROLS...
Page 138
THRESHOLD OF HEARING FOR HEARING FOR CONTINUOUS CONTINUOUS NOISE NOISE 500 1000 2000 4000 8000 500 1000 2000 4000 8000 Frequency at center of sound pressure band (Hz) Frequency at center of sound pressure band (Hz) HIGH HIGH JOHNSON CONTROLS...
Page 139
0.0 3.3 6.6 9.8 13.1 16.4 19.7 23.0 26.2 29.5 32.8 FLOOR FLOOR HORIZONTAL DISTANCE (ft.) HORIZONTAL DISTANCE (ft.) Air conditioner fan speed : Hi Room air temp. : 80qF DB in Cooling mode 68qF DB in Heatin g mode JOHNSON CONTROLS...
7.3 (0.207) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 141
7.3 (0.207) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 142
7.3 (0.207) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 143
9.6 (0.273) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 144
9.6 (0.273) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 145
9.6 (0.273) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
Page 146
Coil resistance (at 20°C) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-18D31 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.10 (0.102) JOHNSON CONTROLS...
Page 147
Coil resistance (at 20°C) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-18D31 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.10 (0.102) JOHNSON CONTROLS...
Page 148
Coil resistance (at 20°C) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-18D31 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.10 (0.102) JOHNSON CONTROLS...
Page 149
Coil resistance (at 20°C) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.8 (0.167) JOHNSON CONTROLS...
Page 150
Coil resistance (at 20°C) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.8 (0.167) JOHNSON CONTROLS...
Page 151
Coil resistance (at 20°C) RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.8 (0.167) JOHNSON CONTROLS...
Page 152
Drain outlet Flange for the air-outlet duct NOTE Make an opening in the housing of the unit so that maintenance service can be peformed on the electric component box, air fi lter, refrigerant tubing connection, and drain pipe. JOHNSON CONTROLS...
Page 153
HEARING FOR HEARING FOR CONTINUOUS CONTINUOUS NOISE NOISE 500 1000 2000 4000 8000 500 1000 2000 4000 8000 Frequency at center of sound pressure band (Hz) Frequency at center of sound pressure band (Hz) HIGH HIGH JOHNSON CONTROLS 4 - 149...
Page 154
0.0 3.3 6.6 9.8 13.1 16.4 19.7 23.0 26.2 29.5 32.8 FLOOR FLOOR HORIZONTAL DISTANCE (ft) HORIZONTAL DISTANCE (ft) Air conditioner fan speed : Hi Room air temp. : 80°F DB in Cooling mode 68°F DB in Heatin g mode JOHNSON CONTROLS...
Page 155
0.118 0.08 0.08 0.079 0.079 0.04 0.04 0.039 0.039 Air Flow (CFM) Air Flow (CFM) FMHX1562/1862 FMHX2462 JFMHX1562N/JFMHX1862N JFMHX2462N 0.118 0.118 0.08 0.08 0.079 0.079 0.04 0.04 0.039 0.039 Air Flow (CFM) Air Flow (CFM) JOHNSON CONTROLS 4 - 151...
fl ow volume for fl exible cylindrical ducts) Airflow (CFM) and the resistance prevalent inside the unit (volume of external Air Flow Volume for Flexible Cylindrical air fed and the resistance within the unit). Duct-Pressure Loss (8) Attaching the External Air Intake Flange JOHNSON CONTROLS...
Page 157
Using values that exceed those shown in the above table will result in noise when only external air is fed being louder than the noise emitted from the indoor unit, so only use values that are within the range of the above values. JOHNSON CONTROLS...
AWG #18 (0.75 mm AWG #18 (0.75 mm AWG #18 (0.75 mm Use shielded wiring* Use shielded wiring Use shielded wiring Max. 3,280 ft. Max. 1,640 ft. Max. 650 ft. (Total) NOTE * With ring-type wire terminal. JOHNSON CONTROLS...
Page 159
“TEST RUN”. Auto address setting can be executed by remote controller automatically. (5) For JK type, if a standard wired remote controller or a simplified remote controller are used, the terminations must be made on the appropriate conductor at the indoor unit. JOHNSON CONTROLS...
Page 160
(3) Refrigerant Circuit (R.C.) address should be set SUPPLY LINE CONTROL before turning the power on. LINE (4) Regarding the R.C. address setting, refer to Section 5 “ TEST RUN ” Auto address setting can be executed by remote controller automatically. JOHNSON CONTROLS...
Page 161
Indoor unit Indoor unit Indoor unit Indoor unit more than 3.3 ft Branch point Indoor unit Indoor unit Indoor unit Indoor unit 16 or fewer more than 3.3 ft Indoor unit less than 3.3 ft Indoor unit Fig. 5-3 JOHNSON CONTROLS...
Page 162
(4) Place the ring pressure terminal, and replace and tighten the removed terminal screw using a screwdriver. Fig. 5-4 (Fig. 5-5) Special Screw washer Ring pressure Screw and terminal Special washer Terminal plate Wire Ring pressure terminal Wire Fig. 5-5 JOHNSON CONTROLS...
Page 163
(field supplied) (field supplied) Earth screw Power wiring (field supplied) Conduit (field supplied) Clamping clip Clamping Power wiring clip Earth screw (field supplied) Remote control wiring Connection for Solenoid and Inter-unit control wiring Valve Kit (for 3WAY) (field supplied) JOHNSON CONTROLS...
Page 164
JT Type Remote control wiring and Inter-unit control wiring (field supplied) Clamping Remote control wiring clip (field supplied) Clamping clip Conduit (field supplied) Earth screw Power wiring Conduit (field supplied) (field supplied) Power wiring Earth screw (field supplied) JOHNSON CONTROLS...
Page 165
(field supplied) wiring (field supplied) (field supplied) Model : JKHX1862N Connection for Solenoid Clamping Valve Kit (for 3WAY) strap Power wiring (field supplied) Earth screw Remote control wiring Conduit and Inter-unit control (field supplied) wiring (field supplied) JOHNSON CONTROLS...
Page 166
Clamping strap NOTE Entirely cover the control Take care not to damage the remote wiring by the wirings (Remote / Inter-unit clasp. Do not leave the remote wiring loose. 3WAYconnection) Remote control wiring and Inter-unit control wiring (field supplied) JOHNSON CONTROLS...
Page 167
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (1) Electric Wiring Diagram JCHX03652N, JCHXR03652N JOHNSON CONTROLS...
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 7. Indoor Unit Wiring Diagrams (1)-1 Electric Wiring Diagram JXHX1252N/JXHX1852N/JXHX2452N/JXHX3652N JOHNSON CONTROLS...
Page 172
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JXHX1252N/JXHX1852N/JXHX2452N/JXHX3652N JOHNSON CONTROLS...
Page 173
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (1)-2 Electric Wiring Diagram JXMHX1252N/JXMHX1852N JOHNSON CONTROLS...
Page 174
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (2) Electric Wiring Diagram JAHX0752N/JAHX0952N/JAHX1252N JOHNSON CONTROLS...
Page 175
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JAHX0752N/JAHX0952N/JAHX1252N JOHNSON CONTROLS...
Page 176
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (3)-1 Electric Wiring Diagram JUHX0762N/JUHX0962N/JUHX1262N/JUHX1562N/JUHX1862N/ JUHX2462N/JUHX3662N/JUHX4862N/JUHX5462N JOHNSON CONTROLS...
Page 177
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JUHX0762N/JUHX0962N/JUHX1262N/JUHX1562N/JUHX1862N/ JUHX2462N/JUHX3662N/JUHX4862N/JUHX5462N JOHNSON CONTROLS...
Page 178
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (3)-2 Electric Wiring Diagram JUMHX0762N/JUMHX0962N/JUMHX1262N/JUMHX1562N/JUMHX1862N JOHNSON CONTROLS...
Page 179
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JUMHX0762N/JUMHX0962N/JUMHX1262N/JUMHX1562N/JUMHX1862N JOHNSON CONTROLS...
Page 180
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (4)-1 Electric Wiring Diagram JDHX3652N JOHNSON CONTROLS...
Page 181
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JDHX3652N JOHNSON CONTROLS...
Page 182
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (4)-2 Electric Wiring Diagram JDHX4852N JOHNSON CONTROLS...
Page 183
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JDHX4852N JOHNSON CONTROLS...
Page 184
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (5) Electric Wiring Diagram JTHX1252N/JTHX1852N/JTHX2452N JOHNSON CONTROLS...
Page 185
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JTHX1252N/JTHX1852N/JTHX2452N JOHNSON CONTROLS...
Page 186
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (6)-1 Electric Wiring Diagram JKHX0752N/JKHX0952N/JKHX1252N JOHNSON CONTROLS...
Page 187
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JKHX0752N/JKHX0952N/JKHX1252N JOHNSON CONTROLS...
Page 188
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (6)-2 Electric Wiring Diagram JKHX1862N JOHNSON CONTROLS...
Page 189
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JKHX1862N JOHNSON CONTROLS...
Page 190
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (6)-4 Electric Wiring Diagram JKHX2452N JOHNSON CONTROLS...
Page 191
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JKHX2452N JOHNSON CONTROLS...
Page 192
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (7) Electric Wiring Diagram JFHX0762N/JFHX0962N/JFHX1262N/JFHX1562N/JFHX1862N/JFHX2462N JOHNSON CONTROLS...
Page 193
FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JFHX0762N/JFHX0962N/JFHX1262N/JFHX1562N/JFHX1862N/JFHX2462N JOHNSON CONTROLS...