Johnson Controls JX Series Engineering Manual

Johnson Controls JX Series Engineering Manual

Mini 2-way variable refrigerant flow vrf system, r410a

Advertisement

MINI 2-WAY
VARIABLE REFRIGERANT FLOW (VRF) SYSTEM
ENGINEERING GUIDE
New Release
Form 121.00-EG1 (512)
MINI 2-WAY
VARIABLE REFRIGERANT FLOW (VRF) SYSTEM
Issue Date:
May 25, 2012

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the JX Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Johnson Controls JX Series

  • Page 1 MINI 2-WAY VARIABLE REFRIGERANT FLOW (VRF) SYSTEM ENGINEERING GUIDE New Release Form 121.00-EG1 (512) MINI 2-WAY VARIABLE REFRIGERANT FLOW (VRF) SYSTEM Issue Date: May 25, 2012...
  • Page 2 ASHRAE 15 ASHRAE 34 The refrigerant (R410A), which is used in the aircon- ditioner, is safe, without the toxicity or combustibil- JOHNSON CONTROLS...
  • Page 3 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 INDOOR UNIT NOMENCLATURE UMHX SERIES CAPACITY SLIM CONCEALED DUCT TYPE JOHNSON CONTROLS OUTDOOR UNIT NOMENCLATURE SERIES CAPACITY SALT-AIR DAMAGE RESISTANT 2-WAY FLOW MINI JOHNSON CONTROLS OUTDOOR UNITS CLASS JCHX Variable Refrigerant Flow JCHX03652N JCHX05252N System...
  • Page 4: Table Of Contents

    7. INDOOR UNIT WIRING DIAGRAMS ........................171 8. CAPACITY RATIO OF OUTDOOR UNITS .......................196 9. COOLING CAPACITY OF INDOOR UNITS .....................204 Note: 1. All data herein is subject to change without notice. 2. Drawings and performance data should not be used for submittal purposes JOHNSON CONTROLS...
  • Page 5: Introduction

    Johnson Controls. You get the freedom to create mediate response to changes in zone loads. With wired comfortable, efficient buildings, without being limited controls, wireless controls and a network portal that by ductwork runs.
  • Page 6 JOHNSON CONTROLS Mini 2-WAY VARIABLE REFRIGERANT FLOW SYSTEM BENEFITS units have a modular design and compact footprint, choosing a Johnson Controls VRF system means easy Johnson Controls Mini 2-way Variable Refrigerant installation and commissioning. With multiple unit Flow (VRF) systems are easy to select with flexibility connectivity, up to 9 indoor units can be connected to built in to the unit choices.
  • Page 7 • Network portal that supports BACnet , LON- ® • 208/230 volt — single-phase power supply WORKS and Johnson Controls N2 protocols. ® • Ceiling, wall and floor mounted models available • Standard operation uses return air sensor, but can • Concealed, semi-concealed and exposed models be configured to use the sensor in the controller.
  • Page 8 • Bottom discharge – should be mounted at least 5’ above the floor and 12” from ceiling • Wireless remote ready – comes with built-in wire- less receiver • Anti-mold washable filter (not MERV rated) • 3-speed AC motor (not ECM) • Condensate pump not included LD16391 JKHX Series - High Wall Mounted Indoor Unit JOHNSON CONTROLS...
  • Page 9 • Pipes can be connected to either side of the unit from the bottom or rear • Wired controller can be mounted in the unit. • Condensate pump not included LD16393 JAHX 1 Way Air Discharge - Semi-Concealed Cassette LD16394 JFHX - Vertical Floor-Mounted Exposed JOHNSON CONTROLS...
  • Page 10 • This unit has a draw-through coil – a P-trap will cal box be required for the condensate • 0.16 in. w.g. static pressure enables ductwork to be fitted • Condensate pump built in LD16398 LD16400 JUMHX - Horizontal Concealed Slim JDHX - High-Static Horizontal Concealed JOHNSON CONTROLS...
  • Page 11 • 7 Day Timer, 6 time periods per day that must be mounted in the field • Temperature set-back • Systems diagnostics capability (with connector cable) • Built in remote temperature sensor LD16497 Wireless Remote Control JOHNSON CONTROLS...
  • Page 12 • Cannot be used for setback – addition of the schedule timer only allows on/off control • Diagnostic history of system past & present • Maximum installation of two System Controls • Requires separate power supply LD16405 LD16407 JSHA-KC64AGN - System Controller JOHNSON CONTROLS...
  • Page 13 ® ® • Only way to control a VRF system with BAS • This allows communication between the propri- etary VRF controls network and the BMS • Field labor is required to add this to the BMS LD16496 JOHNSON CONTROLS...
  • Page 14: Offerings

    JDHX4852N Ceiling-Mounted Type (JT Type) JTHX1252N JTHX1852N JTHX2452N Wall-Mounted Type (JK Type) JKHX0752N JKHX0952N JKHX1252N JKHX1862N JKHX2452N Floor-Standing Type (JF Type) JFHX0762N JFHX0962N JFHX1262N JFHX1562N JFHX1862N JFHX2462N Concealed-Floor Standing Type (JFM Type) JFMHX0762N JFMHX0962N JFMHX1262N JFMHX1562N JFMHX1862N JFMHX2462N JOHNSON CONTROLS...
  • Page 15 Outdoor discharge Unit 96,000 (28.1)96/ 3-29/32 108,000 (31.6) 25/32 1-13/32 2-3/8 4-11/32 2-3/8 5-1/8 JCHX03652/05252 JCHX03652N/05252N JCHXR03652/05252* JCHXR03652N/05252N* * Outdoor unit model name beginning with letters “JCHXR” Refer to the Section 1. Salt-Air Damage Resistant Specifications”. JOHNSON CONTROLS...
  • Page 16 (both sides) ( 80 m) Notes: 1 Consult us before introducing a salt-air damage resistant model as it requires a special treatment. 2 The specifications are subject to change without notice for development. 3 Contact us for the delivery schedule. JOHNSON CONTROLS...
  • Page 17: Outdoor Unit Dimensions And Specifications

    * Full-load conditions at Indoor / Outdoor capacity ratio 100% Cooling : Indoor air temperature 89°F DB / 73°F WB ; Outdoor air temperature 109°F DB / 78°F WB Outdoor unit model name beginning with letters "JCHXR" Refer to the Section 1 "Salt-Ait Damage Resistant Specifications". JOHNSON CONTROLS...
  • Page 18 * Full-load conditions at Indoor / Outdoor capacity ratio 100% Cooling : Indoor air temperature 89°F DB / 73°F WB ; Outdoor air temperature 109°F DB / 78°F WB Outdoor unit model name beginning with letters "JCHXR" Refer to the Section 1 "Salt-Ait Damage Resistant Specifications". JOHNSON CONTROLS...
  • Page 19 Aluminum plate fin / Copper tube Rows...fin pitch in. (mm) 3 ... 7/128 (1.4) Face area 11.7 (1.08) DATA SUBJECT TO CHANGE WITHOUT NOTICE * Outdoor unit model name beginning with letters “JCHXR” Refer to the Section 1 “2. Salt-Air Damage Resistant Specifications”. JOHNSON CONTROLS...
  • Page 20 Aluminum plate fin / Copper tube Rows...fin pitch in. (mm) 3 ... 7/128 (1.4) Face area 11.7 (1.08) DATA SUBJECT TO CHANGE WITHOUT NOTICE * Outdoor unit model name beginning with letters “JCHXR” Refer to the Section 1 “2. Salt-Air Damage Resistant Specifications”. JOHNSON CONTROLS...
  • Page 21 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 1-3. Dimensional Data JCHX03652N, JCHXR03652N JCHX05252N, JCHXR05252N JOHNSON CONTROLS...
  • Page 22 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 1-4. Refrigerant Flow Diagram JCHX03652N JCHX03652 JCHXR03652N JCHXR03652 JCHX05252N JCHX05252 JCHXR05252N JCHXR05252 Suction JOHNSON CONTROLS...
  • Page 23 1000 2000 4000 8000 Frequency at center of sound pressure band (Hz) NOTE 1. dBA = A – weighted sound power level (A – scale according to IEC) 2. Reference acoustic intensity 0 dB = 10 –13 W/ft JOHNSON CONTROLS...
  • Page 24 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 JCHX05252N, JCHXR05252N Model JCHX05252N, JCHXR05252N Sound Power 68 dB (A) Level Cooling Condition NC ‒ 70 NC ‒ 60 NC ‒ 50 NC ‒ 40 NC ‒ 30 NC ‒ 20 1000 2000 4000 8000 Frequency at center of sound pressure band (Hz) NOTE 1. dBA = A ‒  weighted sound power level (A ‒ scale according to IEC) 2. Reference acoustic intensity 0 dB =10  W/ft ‒13 JOHNSON CONTROLS...
  • Page 25 NC – 50 NC – 40 NC – 30 Approximate minimum audible limit for continuous NC – 20 noise 1000 2000 4000 8000 Overall Frequency at center of sound pressure band (Hz) * 0 dB = 0.0002 µbar JOHNSON CONTROLS...
  • Page 26 NC – 50 NC – 40 NC – 30 Approximate minimum audible limit for continuous NC – 20 noise 1000 2000 4000 8000 Overall Frequency at center of sound pressure band (Hz) * 0 dB = 0.0002 µbar JOHNSON CONTROLS...
  • Page 27: Indoor Unit Dimensions And Specifications

    8.1 (0.228) 3.8 (0.104) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 28 8.1 (0.228) 3.8 (0.104) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 29 8.1 (0.228) 3.8 (0.104) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 30 9.9 (0.279) 3.8 (0.104) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 31 4.6 (0.13) 1.7 (0.047) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 32 4.6 (0.13) 1.7 (0.047) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 33 MP24ZN Coil resistance (at 77°F) Ÿ 380 Ÿ ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 34 MP24ZN Coil resistance (at 77°F) Ÿ 380 Ÿ ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 35 MP24ZN Coil resistance (at 77°F) Ÿ 380 Ÿ ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 36 MP24ZN Coil resistance (at 77°F) Ÿ 380 Ÿ ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 37 MP24ZN-12V Coil resistance (at 77°F) Ÿ 380 Ÿ ± 7% / phase Drain pump PLD-12230ST-2 Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 38 MP24ZN-12V Coil resistance (at 77°F) Ÿ 380 Ÿ ± 7% / phase Drain pump PLD-12230ST-2 Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 39 Dimensional Data Dimensional Data Indoor unit: JXHX1252N/JXHX1852N/JXHX2452N 1-3/16 6-19/64 4-23/32 3-13/16 3-15/32 19/32 2-15/16 3-15/32 1-3/8 10-5/64 33-55/64 – 35-53/64 Ceiling opening dimensions 2-23/64 4-29/64 28-15/32 37-13/32 1-49/64 Suspension bolt pitch 20-15/64 15-3/4 6-19/64 15-3/64 3-13/16 4-23/32 8-17/64 7-13/32 JOHNSON CONTROLS...
  • Page 40: 4-Way Air Discharge Ceiling Semi-Concealed, Standard And Mini (Jx, Jxm Type)

    FORM 121.00-EG1 ISSUE DATE: 5/31/2012 5. 4-Way Air Discharge (Mini) Semi-concealed Type (JX, JXM Types) 4-Way Air Discharge Ceiling Semi-Concealed, Standard and Mini (JX, JXM Types) Indoor unit: JXHX3652N JOHNSON CONTROLS...
  • Page 41 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 4-Way Air Discharge Ceiling Semi-Concealed, Standard and Mini (JX, JXM Types) Indoor unit: JXMHX1252N/JXMHX1852N JOHNSON CONTROLS...
  • Page 42 STRONG 41 dB(A) WEAK 33 dB(A) CONDITION 4.9 ft directly below unit NC-50 NC-40 NC-30 Approximate minimum audible NC-20 limit for continuous noise 125 250 1000 2000 4000 8000 Overall Frequency at center of sound pressure band (Hz) JOHNSON CONTROLS...
  • Page 43 0.98 ft/s 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) Cooling : Distribution of temperature (Strong wind : Discharge angle approx.30 ) (Room temperature approx.80°F) 68°F 71°F 75°F 78°F 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
  • Page 44 0.98 ft/s 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) Cooling : Distribution of temperature (Strong wind : Discharge angle approx.30 ) (Room temperature approx.80°F) 68°F 71°F 75°F 78°F 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
  • Page 45 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) Cooling : Distribution of temperature (Strong wind : Discharge angle approx.30 ) (Room temperature approx.80°F) 68°F 71°F 75°F 78°F 16.4 13.1 9.8J 13.1 16.4 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
  • Page 46 0.98 ft/s 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) Cooling : Distribution of temperature (Strong wind : Discharge angle approx.30 ) (Room temperature approx.80°F) 68°F 71°F 75°F 78°F 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
  • Page 47 0.98 ft/s 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) Cooling : Distribution of temperature (Strong wind : Discharge angle approx.30 ) (Room temperature approx.80°F) 68°F 71°F 75°F 78°F 16.4 13.1 13.1 16.4 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
  • Page 48: 1-Way Air Discharge Ceiling Semi-Concealed (Ja Type)

    6.0 (0.170) 2.2 (0.062) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 49 6.0 (0.170) 2.2 (0.062) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 50 6.0 (0.170) 2.2 (0.062) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 51 MP24ZN Coil resistance (at 77°F) Ÿ 380 Ÿ ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 52 MP24ZN Coil resistance (at 77°F) Ÿ 380 Ÿ ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 53 MP24ZN Coil resistance (at 77°F) Ÿ 380 Ÿ ± 7% / phase Drain pump PLD-12230ST Rated V, Hz, W AC230V, 60Hz, 10.8W Total head & capacity ft. (mm), gal/ 2.1 (640), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 54 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 1-Way Air Discharge Ceiling Semi-Concealed (JA Type) Dimensional Data Indoor unit: 7, 9, 12 Type JOHNSON CONTROLS...
  • Page 55 : JAHX1252N MODEL MODEL JAHX0952N SOUND LEVEL : HIGH 36 dB(A) / LOW 31 dB(A) SOUND LEVEL : HIGH 33 dB(A) / LOW 29 dB(A) CONDITION : Under the unit 4.9 ft CONDITION : Under the unit 4.9 ft JOHNSON CONTROLS...
  • Page 56 9.8 13.1 16.4 19.7 23.0 26.2 29.5 32.8 Horizontal distance(ft) (Immediate wind A blow angle 15 degrees) (Room themperature 80 degrees Fahrenheit) Cooling equipment Temperature distribution °F °F °F °F 13.1 9.8 13.1 16.4 19.7 23.0 26.2 29.5 32.8 Horizontal distance(ft) JOHNSON CONTROLS...
  • Page 57: Slim Concealed Duct, Standard And Slim (Ju, Jum Type)

    Shipping volume 8.8 (0.250) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 58 Shipping volume 8.8 (0.250) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 59 Shipping volume 8.8 (0.250) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 60 Shipping volume 8.8 (0.250) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 61 Shipping volume 11.8 (0.334) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 62 Shipping volume 11.8 (0.334) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 63 Shipping volume 16.5 (0.468) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 64 Shipping volume 16.5 (0.468) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 65 Shipping volume 16.5 (0.468) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 66 5.97 (0.169) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 67 5.97 (0.169) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 68 5.97 (0.169) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 69 5.97 (0.169) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 70 5.97 (0.169) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 71 Rows...fi n pitch in. (mm) 2...1 / 16 (1.5) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 72 Rows...fi n pitch in. (mm) 2...1 / 16 (1.5) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 73 Rows...fi n pitch in. (mm) 2...1 / 16 (1.5) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 74 Rows...fi n pitch in. (mm) 3...1 / 16 (1.5) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 75 Rows...fi n pitch in. (mm) 3...1 / 16 (1.5) Face area 2.0 (0.186) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 76 Rows...fi n pitch in. (mm) 3...1 / 16 (1.5) Face area 2.0 (0.186) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 77 Rows...fi n pitch in. (mm) 3...5 / 64 (2.0) Face area 3.3 (0.307) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 78 Rows...fi n pitch in. (mm) 3...5 / 64 (2.0) Face area 3.3 (0.307) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 79 Rows...fi n pitch in. (mm) 3...5 / 64 (2.0) Face area 3.3 (0.307) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC230V, 60Hz, 10.8W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 80 (mm) 3...1/16 (1.4) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC 230 V, 60 Hz, 10.8 W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 81 (mm) 3...1/16 (1.4) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC 230 V, 60 Hz, 10.8 W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 82 (mm) 3...1/16 (1.4) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC 230 V, 60 Hz, 10.8 W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 83 (mm) 3...1/16 (1.4) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC 230 V, 60 Hz, 10.8 W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 84 (mm) 3...1/16 (1.4) Face area 1.2 (0.111) Drain pump ZPLD-12230ST-XH-B Rated V, Hz, W AC 230 V, 60 Hz, 10.8 W ft. (mm), gal/ Total head & capacity 1.6 (500), 0.11 (400) (above drain connection) min (cc/min) JOHNSON CONTROLS...
  • Page 85 Bottom drain port (O.D. 1-1/32") Suspension lug Power supply outlet (ø7/8") Fresh air intake port (ø5-29/32") Flange for the flexible air outlet duct (ø7-7/8") Tube cover Electrical component box Flange for the air intake duct Inter-unit control wiring JOHNSON CONTROLS...
  • Page 86 Bottom drain port (O.D. 1-1/32") Suspension lug Power supply outlet (ø7/8") Fresh air intake port (ø5-29/32") Flange for the flexible air outlet duct (ø7-7/8") Tube cover Electrical component box Flange for the air intake duct (Field supply) Inter-unit control wiring JOHNSON CONTROLS...
  • Page 87 Suspension lug 7-9/32 Power supply outlet (ø7/8") Fresh air intake port (ø5-29/32") Flange for the flexible air outlet duct (ø7-7/8") Tube cover Electrical component box Flange for the air intake duct (Option or field supply) Inter-unit control wiring JOHNSON CONTROLS...
  • Page 88 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Slim Concealed Duct, Standard and Slim (JU, JUM Type) Indoor unit : JUMHX0762N/JUMHX0962N/JUMHX1262N/JUMHX1562N/JUMHX1862N Indoor unit : JUMHX0762N/JUMHX0962N/JUMHX1262N/JUMHX1562N/JUMHX1862N Unit: in. JOHNSON CONTROLS...
  • Page 89 9-41/64 (245) = 29-9/64" (740mm) 9-41/64 (245) + 9-41/64 (245) + 6 x 9-1/16"P (230mmP) 36, 48, 54 Type 58-3/16 56-49/64 18- ø 1/8 9-29/64 (240) + 9-41/64 (245) + 16- ø 15/64 4-23/33 = 54-21/64" (1380mm) 9-41/64 (245) = 48-1/32" (1220mm) JOHNSON CONTROLS...
  • Page 90 Under the unit 4.9 ft. SOURCE : 208 - 230 V, Single-phase, 60 Hz NC-50 NC-40 NC-30 APPROXIMATE NC-20 THRESHOLD OF HEARING FOR CONTINUOUS NOISE 125 250 500 1000 2000 4000 8000 Frequency at center of sound pressure band (Hz) JOHNSON CONTROLS...
  • Page 91 To evaluate the noise level, the maximum value of the measured sound pressure level is used. Read the value at each frequency level (on horizontal axis, center of the sound pressure band) from 63 Hz to 8000 Hz, and select the corresponding maximum value indicated on the vertical axis. JOHNSON CONTROLS...
  • Page 92 To evaluate the noise level, the maximum value of the measured sound pressure level is used. Read the value at each frequency level (on horizontal axis, center of the sound pressure band) from 63 Hz to 8000 Hz, and select the corresponding maximum value indicated on the vertical axis. JOHNSON CONTROLS JOHNSON CONTROLS...
  • Page 93 (Connected booster cable) 1059 1059 1413 1413 1059 Air Flow Volume (CFM) Air Flow Volume (CFM) Air Flow Volume (CFM) Fig. 7-2 Fig. 4-2 NOTE HT : Using the booster cable H : At shipment JOHNSON CONTROLS 4 - 83...
  • Page 94 Upper limit airflow Airflow (CFM) Airflow (CFM) Airflow (CFM) JUMHX1862N JUMHX1262N JUMHX1562N 0.24 0.24 0.20 0.20 0.20 0.197 0.197 0.197 0.16 0.16 0.16 0.12 0.12 0.12 0.08 0.08 0.08 0.04 0.04 0.04 Airflow (CFM) Airflow (CFM) Airflow (CFM) JOHNSON CONTROLS...
  • Page 95 141 (64) Shipping volume 14.8(0.420) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 96 Shipping volume 14.8(0.420) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS JOHNSON CONTROLS...
  • Page 97 Coil resistance (at 68°F) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-30D33 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 4...5 / 64 (2.0) Face area 3.02 (0.281) JOHNSON CONTROLS...
  • Page 98 Coil resistance (at 68°F) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-30D33 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 4...5 / 64 (2.0) Face area 3.02 (0.281) JOHNSON CONTROLS...
  • Page 99 5. Concealed Duct High-Static Pressure Type (D Type) Concealed Duct High Static Pressure (JD Type) Dimensional Data Indoor unit : 36, 48 Type 12-13/64 2-5/32 2-5/32 3-15/16 3-15/16 1-31/32 2-5/32 11-13/16 3-5/32 11-27/64 5-1/8 (Suspension bolt pitch) 3-15/16 3-15/16 3-55/64 1-11/32 JOHNSON CONTROLS...
  • Page 100 To evaluate the noise level, the maximum value of the measured sound pressure level is used. Read the value at each fre- quency level (on horizontal axis, center of the sound pressure band) from 63 Hz to 8000 Hz, and select the corresponding maximum value indicated on the vertical axis. JOHNSON CONTROLS...
  • Page 101: Concealed Duct High Static Pressure (Jd Type)

    36 Type 48 Type (in.WG) (in.WG) 1.00 1.00 0.80 0.80 0.60 0.60 0.40 0.40 0.20 0.20 1059 1236 1059 1236 1412 Air Flow (CFM) Air Flow (CFM) NOTE H : At shipment JOHNSON CONTROLS 4 - 91...
  • Page 102: Ceiling Mounted Exposed Horizontal (Jt Type)

    Shipping volume 7.6 (0.215) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 103 Shipping volume 7.6 (0.215) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 104 Shipping volume 9.7 (0.274) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 105 Coil resistance (at 68°F) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fi n / Copper tube Rows...fi n pitch in. (mm) 3...7/128 (1.4) Face area 1.66 (0.154) JOHNSON CONTROLS...
  • Page 106 Coil resistance (at 68°F) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fi n / Copper tube Rows...fi n pitch in. (mm) 3...7/128 (1.4) Face area 1.66 (0.154) JOHNSON CONTROLS...
  • Page 107 Coil resistance (at 68°F) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fi n / Copper tube Rows...fi n pitch in. (mm) 3...7/128 (1.4) Face area 2.39 (0.222) JOHNSON CONTROLS...
  • Page 108 Left side Right side 8-1/2 2-61/64 3-13/16 (Liquid tubing 9/64 Gas tubing) Liquid 2-23/64 tubing Gas tubing 3-5/16 6-11/32 9-7/8 5-3/4 9-7/8 Left drain position Right drain position Closed with rubber stopper at time of shipment. Unit: in. JOHNSON CONTROLS...
  • Page 109 CONDITION 3.3 ft from front of outlet at height of 4.9 ft NC-50 NC-40 NC-30 Approximate minimum audible NC-20 limit for continuous noise 125 250 1000 2000 4000 8000 Overall Frequency at center of sound pressure band (Hz) JOHNSON CONTROLS...
  • Page 110 Cooling : Distribution of temperature (Strong wind : Discharge angle approx. -7 ) (Room temperature approx.80 F) 68 F 71 F 75 F 78 F 13.1 13.1 16.4 19.7 23.0 26.2 29.5 32.8 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
  • Page 111 Cooling : Distribution of temperature (Strong wind : Discharge angle approx. -7 ) (Room temperature approx.80 F) 68 F 71 F 75 F 78 F 13.1 13.1 16.4 19.7 23.0 26.2 29.5 32.8 Horizontal air flow distance (ft.) JOHNSON CONTROLS...
  • Page 112: Wall Mounted Exposed (Jk Type)

    Shipping volume 3.4 (0.096) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 113 Shipping volume 3.4 (0.096) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 114 Shipping volume 3.4 (0.096) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 115 Shipping volume 4.9 (0.139) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 116 Shipping volume 4.9 (0.139) Rated conditions Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 117 Coil resistance (at 68°F) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 2...7 / 128 (1.3) Face area 2.06 (0.191) JOHNSON CONTROLS...
  • Page 118 Coil resistance (at 68°F) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 2...7 / 128 (1.3) Face area 2.06 (0.191) JOHNSON CONTROLS...
  • Page 119 Coil resistance (at 68°F) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 2...7 / 128 (1.3) Face area 2.06 (0.191) JOHNSON CONTROLS...
  • Page 120 Coil resistance (at 68°F) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 2...1/16 (1.4) Face area 3.54 (0.329) JOHNSON CONTROLS JOHNSON CONTROLS...
  • Page 121 Coil resistance (at 68°F) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminum plate fin / Copper tube Rows...fi n pitch in. (mm) 2...1/16 (1.4) Face area 3.54 (0.329) JOHNSON CONTROLS...
  • Page 122 18, 19, 24 type 44-7/8 Drain hose VP13 (length: Approx. 17-23/32”) ø3/8” ø9.52 Drain and wiring port ø5/8” ø ø3/8” ø Gas tube 15.88) (length: Approx. 19-11/16”) Liquid tube 9.52) (length: Approx. 22-7/16”) unit : in. JOHNSON CONTROLS 4 - 114...
  • Page 123 Overall Overall 125 250 1000 2000 4000 8000 125 250 1000 2000 4000 8000 Frequency at center of sound pressure band (Hz) Frequency at center of sound pressure band (Hz) JOHNSON CONTROLS...
  • Page 124 (Strong / Outlet Angle=60 ) 91 F 4.9 ft/s 86 F 3.9 ft/s 75 F 80 F 2.9 ft/s 0.98 ft/s 2.0 ft/s 0.98 ft/s 13.1 16.4 13.1 16.4 Horizontal air flow distance (ft.) Horizontal air flow distance (ft.) JOHNSON CONTROLS...
  • Page 125: Floor Exposed (Jf Type)

    2.70 (0.251) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 126 2.70 (0.251) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 127 2.70 (0.251) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 128 3.43 (0.319) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 129 3.43 (0.319) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 130 3.43 (0.319) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 131 Coil resistance (at 20°C) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-18D31 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.10 (0.102) JOHNSON CONTROLS...
  • Page 132 Coil resistance (at 20°C) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-18D31 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.10 (0.102) JOHNSON CONTROLS...
  • Page 133 Coil resistance (at 20°C) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-18D31 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.10 (0.102) JOHNSON CONTROLS...
  • Page 134 Coil resistance (at 20°C) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.8 (0.167) JOHNSON CONTROLS...
  • Page 135 Coil resistance (at 20°C) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.8 (0.167) JOHNSON CONTROLS...
  • Page 136 Coil resistance (at 20°C) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.8 (0.167) JOHNSON CONTROLS...
  • Page 137 4-ø15/32" hole (For fastening the indoor unit to the floor by screws.) Air filter Refrigerant connection outlet (liquid tube) Refrigerant connection outlet (gas tube) Level adjusting bolt Drain outlet Power supply outlet (ø7/8) Refrigerant tubing outlet (downward, rear) Location for mounting the remote controller JOHNSON CONTROLS...
  • Page 138 THRESHOLD OF HEARING FOR HEARING FOR CONTINUOUS CONTINUOUS NOISE NOISE 500 1000 2000 4000 8000 500 1000 2000 4000 8000 Frequency at center of sound pressure band (Hz) Frequency at center of sound pressure band (Hz) HIGH HIGH JOHNSON CONTROLS...
  • Page 139 0.0 3.3 6.6 9.8 13.1 16.4 19.7 23.0 26.2 29.5 32.8 FLOOR FLOOR HORIZONTAL DISTANCE (ft.) HORIZONTAL DISTANCE (ft.) Air conditioner fan speed : Hi Room air temp. : 80qF DB in Cooling mode 68qF DB in Heatin g mode JOHNSON CONTROLS...
  • Page 140: Floor Concealed (Jfm Type)

    7.3 (0.207) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 141 7.3 (0.207) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 142 7.3 (0.207) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 143 9.6 (0.273) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 144 9.6 (0.273) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 145 9.6 (0.273) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB JOHNSON CONTROLS...
  • Page 146 Coil resistance (at 20°C) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-18D31 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.10 (0.102) JOHNSON CONTROLS...
  • Page 147 Coil resistance (at 20°C) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-18D31 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.10 (0.102) JOHNSON CONTROLS...
  • Page 148 Coil resistance (at 20°C) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-18D31 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.10 (0.102) JOHNSON CONTROLS...
  • Page 149 Coil resistance (at 20°C) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.8 (0.167) JOHNSON CONTROLS...
  • Page 150 Coil resistance (at 20°C) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.8 (0.167) JOHNSON CONTROLS...
  • Page 151 Coil resistance (at 20°C) Ÿ RED – GRY : 46 BLK – GRY : 46 Valve body UKV-25D32 Heat exchanger Coil Aluminium plate fin / Copper tube Rows...fi n pitch in (mm) 3...5/64 (2.0) Face area 1.8 (0.167) JOHNSON CONTROLS...
  • Page 152 Drain outlet Flange for the air-outlet duct NOTE Make an opening in the housing of the unit so that maintenance service can be peformed on the electric component box, air fi lter, refrigerant tubing connection, and drain pipe. JOHNSON CONTROLS...
  • Page 153 HEARING FOR HEARING FOR CONTINUOUS CONTINUOUS NOISE NOISE 500 1000 2000 4000 8000 500 1000 2000 4000 8000 Frequency at center of sound pressure band (Hz) Frequency at center of sound pressure band (Hz) HIGH HIGH JOHNSON CONTROLS 4 - 149...
  • Page 154 0.0 3.3 6.6 9.8 13.1 16.4 19.7 23.0 26.2 29.5 32.8 FLOOR FLOOR HORIZONTAL DISTANCE (ft) HORIZONTAL DISTANCE (ft) Air conditioner fan speed : Hi Room air temp. : 80°F DB in Cooling mode 68°F DB in Heatin g mode JOHNSON CONTROLS...
  • Page 155 0.118 0.08 0.08 0.079 0.079 0.04 0.04 0.039 0.039 Air Flow (CFM) Air Flow (CFM) FMHX1562/1862 FMHX2462 JFMHX1562N/JFMHX1862N JFMHX2462N 0.118 0.118 0.08 0.08 0.079 0.079 0.04 0.04 0.039 0.039 Air Flow (CFM) Air Flow (CFM) JOHNSON CONTROLS 4 - 151...
  • Page 156: Fresh Air Intake, Semi-Concealed Duct And Concealed Duct Types

    fl ow volume for fl exible cylindrical ducts) Airflow (CFM) and the resistance prevalent inside the unit (volume of external Air Flow Volume for Flexible Cylindrical air fed and the resistance within the unit). Duct-Pressure Loss (8) Attaching the External Air Intake Flange JOHNSON CONTROLS...
  • Page 157 Using values that exceed those shown in the above table will result in noise when only external air is fed being louder than the noise emitted from the indoor unit, so only use values that are within the range of the above values. JOHNSON CONTROLS...
  • Page 158: Electrical Wiring

    AWG #18 (0.75 mm AWG #18 (0.75 mm AWG #18 (0.75 mm Use shielded wiring* Use shielded wiring Use shielded wiring Max. 3,280 ft. Max. 1,640 ft. Max. 650 ft. (Total) NOTE * With ring-type wire terminal. JOHNSON CONTROLS...
  • Page 159 “TEST RUN”. Auto address setting can be executed by remote controller automatically. (5) For JK type, if a standard wired remote controller or a simplified remote controller are used, the terminations must be made on the appropriate conductor at the indoor unit. JOHNSON CONTROLS...
  • Page 160 (3) Refrigerant Circuit (R.C.) address should be set SUPPLY LINE CONTROL before turning the power on. LINE (4) Regarding the R.C. address setting, refer to Section 5 “ TEST RUN ” Auto address setting can be executed by remote controller automatically. JOHNSON CONTROLS...
  • Page 161 Indoor unit Indoor unit Indoor unit Indoor unit more than 3.3 ft Branch point Indoor unit Indoor unit Indoor unit Indoor unit 16 or fewer more than 3.3 ft Indoor unit less than 3.3 ft Indoor unit Fig. 5-3 JOHNSON CONTROLS...
  • Page 162 (4) Place the ring pressure terminal, and replace and tighten the removed terminal screw using a screwdriver. Fig. 5-4 (Fig. 5-5) Special Screw washer Ring pressure Screw and terminal Special washer Terminal plate Wire Ring pressure terminal Wire Fig. 5-5 JOHNSON CONTROLS...
  • Page 163 (field supplied) (field supplied) Earth screw Power wiring (field supplied) Conduit (field supplied) Clamping clip Clamping Power wiring clip Earth screw (field supplied) Remote control wiring Connection for Solenoid and Inter-unit control wiring Valve Kit (for 3WAY) (field supplied) JOHNSON CONTROLS...
  • Page 164 JT Type Remote control wiring and Inter-unit control wiring (field supplied) Clamping Remote control wiring clip (field supplied) Clamping clip Conduit (field supplied) Earth screw Power wiring Conduit (field supplied) (field supplied) Power wiring Earth screw (field supplied) JOHNSON CONTROLS...
  • Page 165 (field supplied) wiring (field supplied) (field supplied) Model : JKHX1862N Connection for Solenoid Clamping Valve Kit (for 3WAY) strap Power wiring (field supplied) Earth screw Remote control wiring Conduit and Inter-unit control (field supplied) wiring (field supplied) JOHNSON CONTROLS...
  • Page 166 Clamping strap NOTE Entirely cover the control Take care not to damage the remote wiring by the wirings (Remote / Inter-unit clasp. Do not leave the remote wiring loose. 3WAYconnection) Remote control wiring and Inter-unit control wiring (field supplied) JOHNSON CONTROLS...
  • Page 167 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (1) Electric Wiring Diagram JCHX03652N, JCHXR03652N JOHNSON CONTROLS...
  • Page 168: Outdoor Unit Wiring Diagrams

    FORM 121.00-EG1 ISSUE DATE: 5/31/2012 6. Outdoor Unit Wiring Diagrams Schematic Diagram JCHX03652N, JCHXR03652N JOHNSON CONTROLS...
  • Page 169 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (2) Electric Wiring Diagram JCHX05252N, JCHXR05252N JOHNSON CONTROLS...
  • Page 170 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JCHX05252N, JCHXR05252N JOHNSON CONTROLS...
  • Page 171: Indoor Unit Wiring Diagrams

    FORM 121.00-EG1 ISSUE DATE: 5/31/2012 7. Indoor Unit Wiring Diagrams (1)-1 Electric Wiring Diagram JXHX1252N/JXHX1852N/JXHX2452N/JXHX3652N JOHNSON CONTROLS...
  • Page 172 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JXHX1252N/JXHX1852N/JXHX2452N/JXHX3652N JOHNSON CONTROLS...
  • Page 173 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (1)-2 Electric Wiring Diagram JXMHX1252N/JXMHX1852N JOHNSON CONTROLS...
  • Page 174 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (2) Electric Wiring Diagram JAHX0752N/JAHX0952N/JAHX1252N JOHNSON CONTROLS...
  • Page 175 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JAHX0752N/JAHX0952N/JAHX1252N JOHNSON CONTROLS...
  • Page 176 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (3)-1 Electric Wiring Diagram JUHX0762N/JUHX0962N/JUHX1262N/JUHX1562N/JUHX1862N/ JUHX2462N/JUHX3662N/JUHX4862N/JUHX5462N JOHNSON CONTROLS...
  • Page 177 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JUHX0762N/JUHX0962N/JUHX1262N/JUHX1562N/JUHX1862N/ JUHX2462N/JUHX3662N/JUHX4862N/JUHX5462N JOHNSON CONTROLS...
  • Page 178 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (3)-2 Electric Wiring Diagram JUMHX0762N/JUMHX0962N/JUMHX1262N/JUMHX1562N/JUMHX1862N JOHNSON CONTROLS...
  • Page 179 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JUMHX0762N/JUMHX0962N/JUMHX1262N/JUMHX1562N/JUMHX1862N JOHNSON CONTROLS...
  • Page 180 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (4)-1 Electric Wiring Diagram JDHX3652N JOHNSON CONTROLS...
  • Page 181 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JDHX3652N JOHNSON CONTROLS...
  • Page 182 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (4)-2 Electric Wiring Diagram JDHX4852N JOHNSON CONTROLS...
  • Page 183 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JDHX4852N JOHNSON CONTROLS...
  • Page 184 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (5) Electric Wiring Diagram JTHX1252N/JTHX1852N/JTHX2452N JOHNSON CONTROLS...
  • Page 185 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JTHX1252N/JTHX1852N/JTHX2452N JOHNSON CONTROLS...
  • Page 186 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (6)-1 Electric Wiring Diagram JKHX0752N/JKHX0952N/JKHX1252N JOHNSON CONTROLS...
  • Page 187 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JKHX0752N/JKHX0952N/JKHX1252N JOHNSON CONTROLS...
  • Page 188 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (6)-2 Electric Wiring Diagram JKHX1862N JOHNSON CONTROLS...
  • Page 189 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JKHX1862N JOHNSON CONTROLS...
  • Page 190 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (6)-4 Electric Wiring Diagram JKHX2452N JOHNSON CONTROLS...
  • Page 191 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JKHX2452N JOHNSON CONTROLS...
  • Page 192 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (7) Electric Wiring Diagram JFHX0762N/JFHX0962N/JFHX1262N/JFHX1562N/JFHX1862N/JFHX2462N JOHNSON CONTROLS...
  • Page 193 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JFHX0762N/JFHX0962N/JFHX1262N/JFHX1562N/JFHX1862N/JFHX2462N JOHNSON CONTROLS...
  • Page 194 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 (8) Electric Wiring Diagram JFMHX0762N/JFMHX0962N/JFMHX1262N/JFMHX1562N/JFMHX1862N/JFMHX2462N JOHNSON CONTROLS...
  • Page 195 FORM 121.00-EG1 ISSUE DATE: 5/31/2012 Schematic Diagram JFMHX0762N/JFMHX0962N/JFMHX1262N/JFMHX1562N/JFMHX1862N/JFMHX2462N JOHNSON CONTROLS...
  • Page 196: Capacity Ratio Of Outdoor Units

    2.35 11.4 2.51 11.8 2.60 35.0 1.76 1.95 2.13 10.1 2.35 10.7 2.53 11.1 2.67 11.4 2.77 40.0 2.06 2.25 2.44 2.70 10.2 2.77 10.6 2.84 10.9 2.91 43.0 2.35 2.53 2.65 2.77 2.86 10.1 2.96 10.5 3.00 JOHNSON CONTROLS...
  • Page 197 0.63 0.70 0.78 0.83 0.89 1.03 30.0 0.64 0.71 0.78 0.87 0.99 1.06 1.10 35.0 0.75 0.82 0.90 0.99 1.07 1.13 1.17 40.0 0.87 0.95 1.03 1.14 1.17 1.20 1.23 43.0 0.99 1.07 1.12 1.17 1.21 1.25 1.27 JOHNSON CONTROLS...
  • Page 198 2.51 11.3 2.46 10.9 2.36 10.1 2.13 1.88 11.2 10.0 13.2 2.94 12.4 2.69 11.6 2.36 11.3 2.31 10.9 2.20 10.1 1.98 1.72 16.4 15.0 13.2 2.66 12.4 2.41 11.6 2.05 11.3 2.00 10.9 1.90 10.1 1.72 1.42 JOHNSON CONTROLS...
  • Page 199 1.51 1.33 1.31 1.23 1.14 1.01 1.60 1.48 1.29 1.27 1.20 1.10 0.98 1.55 1.43 1.25 1.23 1.18 1.06 0.94 11.2 10.0 1.47 1.34 1.18 1.15 1.10 0.99 0.86 16.4 15.0 1.33 1.20 1.03 1.00 0.95 0.86 0.71 JOHNSON CONTROLS...
  • Page 200 14.0 3.84 14.5 3.92 15.1 4.03 15.6 4.15 40.0 11.2 3.38 12.1 3.69 13.0 3.99 12.6 4.11 13.5 4.15 14.2 4.26 14.6 4.41 43.0 11.2 3.84 11.2 4.07 11.2 4.15 11.2 4.22 12.6 4.34 13.4 4.41 14.0 4.53 JOHNSON CONTROLS...
  • Page 201 1.00 1.11 1.23 1.42 1.53 1.52 30.0 1.01 1.12 1.23 1.39 1.49 1.55 1.61 35.0 1.19 1.31 1.44 1.58 1.61 1.66 1.71 40.0 1.39 1.52 1.64 1.69 1.71 1.76 1.82 43.0 1.58 1.68 1.71 1.74 1.79 1.82 1.87 JOHNSON CONTROLS...
  • Page 202 15.3 3.67 14.3 3.35 13.1 2.95 11.2 10.0 18.5 4.66 17.4 4.22 16.4 3.83 15.8 3.63 15.3 3.43 14.3 3.11 13.1 2.67 16.4 15.0 18.5 4.18 17.4 3.79 16.4 3.35 15.8 3.15 15.3 2.95 14.3 2.63 13.1 2.23 JOHNSON CONTROLS...
  • Page 203 1.73 1.54 10.1 2.35 2.23 2.02 1.92 1.83 1.67 1.48 10.3 2.37 2.15 1.96 1.87 1.77 1.62 1.42 11.2 10.0 10.3 2.25 2.04 1.85 1.75 1.65 1.50 1.29 16.4 15.0 10.3 2.02 1.83 1.62 1.52 1.42 1.27 1.08 JOHNSON CONTROLS...
  • Page 204: Cooling Capacity Of Indoor Units

    Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 15.5 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 205 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW AIR FLOW 16.0 m /min RATING CAPACITY: CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 206 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) RATING CAPACITY: 7.3 kW AIR FLOW 20.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 207 11.7 11.5 11.3 11.1 10.9 10.7 10.4 10.1 12.7 12.7 12.7 12.7 12.6 12.4 12.3 12.1 12.0 11.8 11.5 11.3 11.1 10.8 10.6 13.4 13.4 13.3 13.2 13.1 13.0 12.8 12.6 12.5 12.3 12.1 11.8 11.6 11.3 11.1 JOHNSON CONTROLS...
  • Page 208 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) RATING CAPACITY: 3.6 kW AIR FLOW 9.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 209 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW RATING CAPACITY: AIR FLOW 12.5 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 210 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.2 kW RATING CAPACITY: AIR FLOW 8.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 211 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.8 kW RATING CAPACITY: AIR FLOW 8.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 212 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 9.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 213 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.2 kW RATING CAPACITY: AIR FLOW 10.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 214 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.8 kW RATING CAPACITY: AIR FLOW 10.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 215 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 10.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 216 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.3 kW RATING CAPACITY: AIR FLOW 16.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 217 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 7.3 kW RATING CAPACITY: AIR FLOW 16.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 218 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 12.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 219 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW RATING CAPACITY: AIR FLOW 13.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 220 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 7.3 kW RATING CAPACITY: AIR FLOW 18.5 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 221 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.2 kW RATING CAPACITY: AIR FLOW 10.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 222 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.8 kW RATING CAPACITY: AIR FLOW 10.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 223 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 10.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 224 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 4.5 kW RATING CAPACITY: AIR FLOW 12.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 225 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW RATING CAPACITY: AIR FLOW 12.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 226 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 7.3 kW RATING CAPACITY: AIR FLOW 19.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 227 11.7 11.5 11.3 11.1 10.9 10.7 10.4 10.1 12.7 12.7 12.7 12.7 12.6 12.4 12.3 12.1 12.0 11.8 11.5 11.3 11.1 10.8 10.6 13.4 13.4 13.3 13.2 13.1 13.0 12.8 12.6 12.5 12.3 12.1 11.8 11.6 11.3 11.1 JOHNSON CONTROLS...
  • Page 228 10.2 10.1 10.0 16.8 16.8 16.8 16.7 16.6 16.4 16.2 16.0 15.8 15.5 15.3 15.0 14.6 14.3 13.9 10.1 10.1 10.1 10.1 10.1 17.7 17.7 17.6 17.4 17.3 17.1 16.9 16.7 16.5 16.2 15.9 15.6 15.3 15.0 14.6 JOHNSON CONTROLS...
  • Page 229 11.3 11.2 11.1 11.1 10.9 10.9 10.7 10.6 10.5 10.3 10.1 10.0 20.3 20.2 20.1 19.9 19.7 19.5 19.3 19.1 18.8 18.5 18.2 17.9 17.5 17.1 16.7 10.9 10.9 10.8 10.7 10.7 10.6 10.5 10.4 10.3 10.1 10.0 JOHNSON CONTROLS...
  • Page 230 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.2 kW RATING CAPACITY: AIR FLOW 8.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 231 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.8 kW RATING CAPACITY: AIR FLOW 8.5 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 232 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 9.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 233 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 4.5 kW RATING CAPACITY: AIR FLOW 10.5 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 234 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW RATING CAPACITY: AIR FLOW 12.5 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 235 11.7 11.5 11.3 11.1 10.9 10.7 10.4 10.1 12.7 12.7 12.7 12.7 12.6 12.4 12.3 12.1 12.0 11.8 11.5 11.3 11.1 10.8 10.6 13.4 13.4 13.3 13.2 13.1 13.0 12.8 12.6 12.5 12.3 12.1 11.8 11.6 11.3 11.1 JOHNSON CONTROLS...
  • Page 236 11.3 11.2 11.1 11.1 10.9 10.9 10.7 10.6 10.5 17.7 17.7 17.6 17.4 17.3 17.1 16.9 16.7 16.5 16.2 15.9 15.6 15.3 15.0 14.6 10.9 10.9 10.9 10.9 10.8 10.7 10.6 10.6 10.5 10.4 10.3 10.2 10.1 10.0 JOHNSON CONTROLS...
  • Page 237 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.2 kW RATING CAPACITY: AIR FLOW 7.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 238 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.8 kW RATING CAPACITY: AIR FLOW 7.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 239 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 9.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 240 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 4.5 kW RATING CAPACITY: AIR FLOW 12.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 241 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW RATING CAPACITY: AIR FLOW 15.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 242 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 7.1 kW RATING CAPACITY: AIR FLOW 17.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 243 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.2 kW RATING CAPACITY: AIR FLOW 7.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 244 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.8 kW RATING CAPACITY: AIR FLOW 7.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 245 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 9.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 246 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 4.5 kW RATING CAPACITY: AIR FLOW 12.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS JOHNSON CONTROLS...
  • Page 247 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW RATING CAPACITY: AIR FLOW 15.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 248 JFMHX2462N Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) RATING CAPACITY: AIR FLOW 17.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP. ( W.B. D.B. JOHNSON CONTROLS...
  • Page 249 P.O. Box 1592, York, Pennsylvania USA 17405-1592 800-861-1001 Subject to change without notice. Printed in USA Copyright © by Johnson Controls 2012 www.johnsoncontrols.com ALL RIGHTS RESERVED Form 120.00-EG1 (512) Issue Date: May 31, 2012 NEW RELEASE...