9. Concealed Floor-Standing Type (FM Type)
Floor Concealed (JFM Type)
Unit specifi cations (F)
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity
Air circulation (Hi / Me / Lo)
Moisture removal (High)
ELECTRICAL RATINGS
Voltage rating
Available voltage range
Running amperes
Power input
Power factor
Max. starting amperes
FEATURES
Controls
Timer
Fan speeds
Air fi lter
Refrigerant control
Operation sound (Hi / Me / Lo)
Refrigerant tubing connections
Liquid tube
Refrigerant tube
diameter
Gas tube
Drain connection
Remote controller
Refrigerant tubing kit / Accessories
Color (Approximate value)
DIMENSIONS & WEIGHT
Height
Unit dimensions
Width
Depth
Net weight
Shipping weight
Shipping volume
Rated conditions
Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB
Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB
145
Indoor Unit
BTU / h
kW
CFM
Pints / h
V
V
A
W
%
A
dB-A
in. (mm)
in. (mm)
in. (mm)
in. (mm)
in. (mm)
lbs. (kg)
lbs. (kg)
3
3
ft
(m
)
JFMHX2462N
208 - 230 V / 1ø / 60 Hz
Cooling
24,000
7.1
601 / 495 / 424
7.4
208
230
187 - 253
0.56
0.60
110
129
94
94
1
1
Microprocessor
ON / OFF Timer (Max. 72 hr)
3 and Automatic control
Washable, easy access
Electronic expansion valve
41 / 38 / 35
Flare type
3 / 8 (9.52)
5 / 8 (15.88)
OD 1-1/4"
Optional (Wired / Wireless)
Optional / –
–
Unit dimensions
24-1 / 4 (616)
48 (1219)
9-1 / 32 (229)
62 (28)
68 (31)
9.6 (0.273)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
FORM 121.00-EG1
ISSUE DATE: 5/31/2012
Heating
27,000
8.0
–
208
230
187 - 253
0.56
0.58
109
125
93
94
1
1
Package dimensions
26-23 / 32 (679)
50-13 / 16 (1291)
12-9 / 32 (312)