IBM i Series Handbook page 105

Connecting to operations console
Hide thumbs Also See for i Series:
Table of Contents

Advertisement

4.
Select the communications port being used for the console. It might also be listed as direct to
COMn (where n is 1 to 4). Click OK.
Note: If you have a problem accessing the PC's serial port, you might have to power off the PC and
|
|
then restart it to reset the hardware port.
5. A COMn Properties window will appear. Change the speed to 9600. Click OK.
Note: Failure to set the speed to 9600 will result in all unintelligible text and you will not see the
desired results.
6. The HyperTerminal window will open. In the lower-left corner the status should report as
Connected and the time will be incrementing.
7. In the data window you may get:
v Nothing
v Unintelligible
v +++ATH0
8. Do a Disconnect.
9. Select File → Properties.
10. You should be in the Properties for the connection you just created. Select the Settings tab.
11. Click ASCII Setup.
12. Change the following settings so there is a check mark in the check box:
v Send line ends with line feeds
v Echo typed characters locally
v Append line feeds to incoming line ends
v Wrap lines that exceed terminal width
13. Click OK. Click OK.
14. Do a Connect.
15. At the system's control panel, enter function 65 (you need to take the system to a known state).
Note: You may need to enter function 25 and 26 in order to have access to the upper functions.
16. The system's control panel might display D1008065 after a while. Also, in the HyperTerminal
window, you might receive some data.
17. At the system's control panel, enter function 66. You might see D1008066. Also, in the HyperTerminal
window, you might receive some data.
18. Using uppercase, type NEGOTIATE 1 in the HyperTerminal window. Press Enter. The HyperTerminal
data window displays 115200.
Note: If nothing is returned, repeat NEGOTIATE 1.
If a speed value is returned, you had data exchanged in both directions and have full connectivity. If
Operations Console will not connect, more than likely you have a setup problem on the client side.
If a speed value is not returned, you might try turning off the PC, turn it back on, and repeat the
test. Alternatively, you can try connecting to the console again. In rare cases, the system might need
an IPL. For the best results, it is suggested that you follow these steps:
a. Turn off the system.
b. Turn off the PC.
c. Turn on the PC.
d. Start a connection for the console.
e. Turn on the system.
93
Operations Console

Advertisement

Table of Contents
loading

Table of Contents