Configuring the VLT 5000 with RS Networx
Double click on the VLT 5000.
Click on EDS I/O default. Here is shown that VLT
5000 support Polled I/O.
The actual PPO type is type 1 using 4 byte Input
and 4 byte Output.
The PPO type can be changed in parameter 904
PPO Selection.
Parameter
Polled Size
904
Rx
PPO1
4 Bytes
PPO2
8 Bytes
PPO3
4 Bytes
PPO4
8 Bytes
The 4 byte Input is Status word and Main Actual
Value from the VLT 5000.
The 4 byte Output is Control word and reference to
the VLT 5000.
Click on OK
MN.51.T1.02 - VLT is a registered Danfoss trademark
VLT
®
5000 DeviceNet and Allen Bradley Control logix 5550
Double click on the 1756-DNB Scanner.
Click on Scanlist and add VLT 5000 from Available
Devices to the Scanlist.
Click on Input and if you click on AutoMap the I/O
area of VLT 5000 will be added to the first free area,
here I 0.0. This means that the Status word will be
Polled Size
read from the VLT 5000 to I/O area I:0.0 to I:0.15
Tx
and the Main Actual Reference to I:0.16 to I:0.32.
4 Bytes
Do the same with the Output to map Control word
and reference.
8 Bytes
4 Bytes
8 Bytes
Save the file and download the RS networx to the
Scanner.