Tzidc-220 - ABB TZIDC-200 Commissioning Instructions

Electro-pneumatic positioner
Hide thumbs Also See for TZIDC-200:
Table of Contents

Advertisement

Ex relevant specifications
IECEx
Type-Examination Test
Certificate:
Type:
Temperature class:
Permissible ambient temperature:
Signal circuit for PROFIBUS PA only for connecting a certified
intrinsically safe circuit (e.g., FISCO power supply or barriers) with
max. values acc. to:
FISCO power
supply ia/ib
for Grp. IIB/IIC
Voltage
Ui = 17.5 V
Current
li = 380 mA
Power
Pi = 5.32 W
Characteri
rectangular
stic
7.3

TZIDC-220

FM Approval HLC 7/04 3019164
Explosion proof; enclosure 4X; T5, max. 82 °C
CL I; Div 1; Grp. C-D
Dust ignition-proof; enclosure 4X; T5; max. 82 °C
CL II, III, Div 1 Grp. E-F-G
CSA Certification 1555690
Explosion proof; enclosure 4X
Temperature range: -40 ... 85 °C
T5, max. 85 °C ; T6, max. 70 °C
CL I; Div 1; Grp. C-D
CL II; Div 1; Grp. E-F-G
CL III
Change from one to two columns
30 - EN
Ex ia IIC T6
IECEx TUN 04.0015X, Issue no.:
0
Intrinsically safe
T4, T5, T6
T4: -40 °C < T
< 85 °C
amb
T5: -40 °C < T
< 55 °C
amb
T6: -40 °C < T
< 40 °C
amb
FISCO power
Barriers or
supply ia/ib
power supply
for Grp. IIB/IIC
ia/ib for Grp.
IIB/IIC
Ui = 17.5 V
Ui = 24 V
li = 360 mA
li = 250 mA
Pi = 2.52 W
Pi = 1.2 W
trapezoidal
Linear
TZIDC-200, TZIDC-210, TZIDC-220
ATEX / GOST Ukraine
Type-Examination Test
Certificate:
Type:
Device class:
Temperature class:
Permissible ambient
temperature:
ATEX
Prototype test certificate:
Type:
Device class:
Temperature class:
Permissible ambient
temperature:
IECEx
Prototype test certificate:
Type:
Temperature class:
Permissible ambient
temperature:
Signal circuit for FOUNDATION fieldbus only for connecting a
certified intrinsically safe circuit (e.g., FISCO power supply or
barriers) with max. values acc. to:
FISCO power
supply ia/ib
for Grp. IIB/IIC
Voltage
Ui = 17.5 V
Current
li = 380 mA
Power
Pi = 5.32 W
Characteri
rectangular
stic
II 2G EEx d II C T4/T5/T6
DMT 02 ATEX E 029 X
Flameproof enclosure for
equipment
II 2G (EEx ib IIC)
T4, T5, T6
T4: -40 °C < T
< 85 °C
amb
T5: -40 °C < T
< 80 °C
amb
T6: -40 °C < T
< 65 °C
amb
II 2G EEx ia IIC T6
TÜV 02 ATEX 1831 X
Intrinsically safe equipment
II 2G (EEx ia IIC)
T4, T5, T6
< 85 °C
T4: -40 °C < T
amb
T5: -40 °C < T
< 55 °C
amb
T6: -40 °C < T
< 40 °C
amb
Ex ia IIC T6
IECEx TUN 04.0015X, Issue no.: 0
Intrinsically safe
T4, T5, T6
T4: -40 °C < T
< 85 °C
amb
T5: -40 °C < T
< 55 °C
amb
T6: -40 °C < T
< 40 °C
amb
FISCO power
Barriers or
supply ia/ib
power supply
for Grp. IIB/IIC
ia/ib for Grp.
IIB/IIC
Ui = 17.5 V
Ui = 24 V
li = 360 mA
li = 250 mA
Pi = 2.52 W
Pi = 1.2 W
trapezoidal
Linear
CI/TZIDC-200/210/220-EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tzidc-210Tzidc-220

Table of Contents