3

Mounting

Caution - Risk of injury!
Incorrect parameter values can cause the valve to move unexpectedly. This can lead to
process failures and result in injuries.
Before recommissioning a TZIDC-200, TZIDC-210, TZIDC-220 positioner that was used at
another location, the device must always be reset to factory settings. Never start Autoadjust
before restoring factory settings.
3.1

Operating conditions at installation site

Important
Before installation, check whether the TZIDC-200, TZIDC-210, TZIDC-220 positioner meets
the control and safety requirements for the installation location (actuator or valve).
See the „Specifications" chapter in the operating instructions or on the data sheet.
3.2

Mechanical mount

cke
3.2.1

General

Fig. 2: Operating range
The arrow (1) on the positioner feedback shaft (and the lever) must move through the area
marked by the arrows (2).