Diagram Of Water Side Head Losses; Determination Of The Primary Circuit Pump Or Boiler Pump - Immergas ARES PRO 150 Instructions And Recommendations

High condensate water storage generator
Table of Contents

Advertisement

2.3
DIAGRAM OF WATER SIDE HEAD
LOSSES
2.3.1
DETERMINATION OF THE PRIMARY CIRCUIT PUMP
OR BOILER PUMP
The boiler pump must have head that can ensure circulator flow rates
according to the circuit's ∆.
The pumps must be determined by the installer or
designer based on the data for the boiler and system.
ARES PRO
Maximum flow rate in l/h (∆t=15K)
Nominal requested flow rate in l/h (∆t = 20K)
ARES PRO
150
ARES PRO
300
ARES PRO
230
ARES PRO
348 - 400 -
500
ARES PRO
150
7,818
5,863
Technical features and dimensions
600
The pump is not an integral part of the boiler.
It is advisable to choose a pump with a flow rate and head of approx-
imately 2/3 of its typical curve.
230
300
11,999
15,740
19,575
9,000
11,805
14,681
13
Flow rate (m3/h)
348
400
500
21,386
25,338
16,039
19,004
600
30,978
23,234