Section 4: Initial Inspection And Installation; Introduction; Manual Operation Check; Vacuum Interrupter Integrity - Eaton 380 VCP-Wind Instructions For The Use, Operation And Maintenance

Vacuum circuit breakers
Table of Contents

Advertisement

I.B. 70A2580H02
SECTION 4: INITIAL INSPECTION AND
INSTALLATION

4-1 INTRODUCTION

BEFORE PLACING THE CIRCUIT BREAKER IN
SERVICE, CAREFULLY FOLLOW THE
INSTALLATION PROCEDURE GIVEN BELOW. NOT
FOLLOWING THE PROCEDURE CAN FAIL TO
UNCOVER SHIPPING DAMAGE THAT MAY RESULT
IN INCORRECT CIRCUIT BREAKER OPERATION
LEADING TO DEATH, BODILY INJURY, AND
EQUIPMENT DAMAGE.
Before attempting to place a circuit breaker in service, it
should be carefully examined and operated manually and
electrically. In addition, carefully examine the breaker for
loose or obviously damaged parts. The following
information is a guide for performing recommended
checks and tests.

4-2 MANUAL OPERATION CHECK

Refer to Figures 3-4 and 4-1 and then proceed by placing
the maintenance tool into the manual charge socket
opening. Charge the closing springs with about 36 up
and down strokes of the handle. When charging is
complete the closing crank goes over center with an
audible CLICK and the springs Charged/Discharged
indicator shows "Charged."
NOTICE
If the springs are to be charged on a closed circuit
breaker, no click is heard at the end of charging
operation. Discontinue charging and remove the
maintenance tool as soon as "Charged" flag is fully
visible. Continued attempts to charge further may
result in damage to the mechanism.
Remove the maintenance tool. Close and trip the circuit
breaker. Repeat several times.

4-3 VACUUM INTERRUPTER INTEGRITY

Using a dry, lint free cloth or paper towel, clean all the
accessible insulating surfaces of the pole units. Conduct a
vacuum interrupter integrity check as described in
Section 6-4.
Effective November 2012
WARNING

4-4 INSULATION

Check the circuit breaker's primary and secondary
insulation as described in Section 6-6.

4-5 CONTACT EROSION AND WIPE

Eaton vacuum interrupters used on the 38kV VCP-
Wind are designed to achieve very low arc voltages
and short arc times, resulting in very low arc
energy. Contact wear is therefore negligible.

4-6 PRIMARY CIRCUIT RESISTANCE

Check the primary circuit resistance as described in
Section 6-7. The resistance should not exceed the
values specified. Record the values obtained for
future reference.

4-7 NAMEPLATE

Compare the circuit breaker nameplate information
with switchgear drawings for compatibility.

4-8 ELECTRICAL OPERATION CHECK

After having completed all previous checks and tests,
the circuit breaker is ready to be operated electrically.
It is preferred that this check be made with the circuit
breaker in the TEST position or by using a test
jumper, if the circuit breaker is outside the cell
structure.
Figure 4-1 Type VCP-Wind Circuit Breaker Manual
Charging Handle in Use
Page 11

Advertisement

Table of Contents
loading

Table of Contents