Section 2: Installation Of Pop-Out Trip Indicator - Eaton NRX Series Instruction Leaflet

Pop-out trip indicators
Hide thumbs Also See for NRX Series:
Table of Contents

Advertisement

Series NRX with PXR - instructions for
pop-out trip indicators
Table 1. Remote reset ratings
Control voltage
Frequency
24
DC
110–127
50–60 Hz
110–125
DC
208–240
50–60 Hz
220–250
DC
Red plunger
Figure 4.
Remote reset interlock indicator shown.
Section 2: Installation of pop-out trip
indicator
Proceed with the following nine steps.
Step 1: Remove the four screws holding the front cover in place (two
on each side of the cover).
Figure 5. Step 1.
Step 2: Remove the front cover. Pull down on the charging handle to
simplify removal.
Operational voltage (range 70–110%)
17–26
77–140
77–138
146–264
154–275
Instruction Leaflet IL0131126EN
Inrush power consumption (VA)
500
540
540
500
515
Figure 6. Step 2.
Step 3: Remove the plug in the breaker cover. This will allow the red
plunger to pass through the cover.
Figure 7.
Step 3.
Step 4: Slide the left accessory tray (used for mounting accessories
such as ST, UVR, and OTS) approximately 1 in. (25.4mm) to the left
by depressing the thumb tab and sliding the tray out. This will create
sufficient room to install the trip indicator.
Effective May 2016
Reset closing time (ms)
25
25
25
25
25
Plug
EATON www.eaton.com
3