Figure 6-10 Manually Closing Circuit Breaker with
Marker in Hole "C".
Figure 6-11 Top View of Cam and Marker Interface
Figure 6-12 Move Marker 15° to Right
Step 10 - Remove the marker from hole
Step 11 - Push the "push to open" clapper to open the
circuit breaker.
Step 12 - Inspect the circuit breaker to assure it is in the
Effective November 2012
70A2580H02
Printed in USA
Figure 6-13 Move Marker 15° to left
Figure 6-14 Remove Marked Masking Tape from
Cam
Figure 6-15 Place Tape on Right Side Panel of
Breaker
open position and the closing springs are discharged.
"C".
Remove the transparent CloSure
tape from the cam and stick the tape on the front right
side sheet of the circuit breaker. Record the date of
the test and the operations counter reading on the
tape (Figures
I.B. 70A2580H02
TM
Tool. Remove the
and
and
6-1 4
6-15
6-16) .