5.0 SITE LOCATION & PREPARATION

5.1 Site Location.

The wall, floor or plinth for the boilers, frames & water manifold kit must be both flat & level to ensure correct
alignment of fittings & connections.
The wall or floor must be sufficiently strong to support the weight of both the boilers & manifold kit where used.
The wall or floor must be fireproof in accordance with BS 6644.
The plantroom must have sufficient space for installation of boilers, manifold kits, pipework, pumps, controls, flues,
ventilation, access & servicing, & other items of plant.

5.2 Gas Supply.

Gas supply pipes must be in accordance with BS 6891 or IGE/UP/2
Gas supply connection to the boiler must not be smaller than the connection on the boiler - Rp 3/4"
Gas installation must be soundness tested to BS 6891 or IGE/UP/1 & IGE/UP/1A.
Gas installation must be purged to BS 6891 or IGE/UP/1 & IGE/UP/1A.
Inlet gas pressure to boiler for Natural Gas should be nominal 20mbar (minimum 17.5mbar) dynamic at the
connection to the boiler. Refer to Appendix A for LPG.
Boiler house gas isolation valve must be clearly identified & installed close to the entrance / exit.
5.3 Water Supply & Return
Feed & Expansion tanks to comply with static height requirements of BS6880 & BS6644.
Cold feed & open vent pipes to comply with requirements of BS 6644.
Pressurised system to comply with BS 7074.
It is recommended that the system pipework is flushed twice before water treatment.
In hard water areas (>180mg CaCO
prevent the build up of sludge and scale and also to control the system water pH to between 7.0 & 8.0.
Leaks in the system pipework should be fixed to prevent dilution of water treatment.
Maximum working water pressure is 7 bar.
For minimum water pressure see Appendix E .