Unplug the 2 connectors from the fan & gas valve.
Disconnect the 15mm gas connection to the gas valve inlet.
Remove the 4 screws/nuts securing the fan/venturi/gas valve assembly to the transition duct.
Withdraw the assembly from the air inlet duct.
Remove the 25 screws securing the venturi/gas valve assembly to the fan (note the cork sealing gasket).
Re-assemble in reverse order using new gaskets where necessary.
Ensure all screws are tightened & electrical plugs are firmly & correctly located.
Re-light the boiler, check & adjust the combustion as detailed in Section 7.
11.6 Main control PCB
Part No. 533901508 – (SE64he) Nat Gas
Part No. 533901xzy – (SE71c) Nat Gas
Part No. 533901yzx – (SE64he) LPG
Part No. 533901yxz – (SE71c) LPG
Remove the 2 screws which secure the fascia panel to the controls panel body.
Carefully withdraw the fascia panel & hang it on the two hooks on the control panel body.
Disconnect the plug connectors from the main PCB.
These are polarised to ensure correct engagement.
Carefully remove the screws securing the pcb to the panel & withdraw the control.
Re-assemble in reverse order.
Re-light the boiler & check for operation.