Quik-drive voltage regulator tap-changer
Table of Contents

Advertisement

Placing tap-changer into neutral
1.
Place a 3/8" socket and ratchet on the output shaft of
the motor; rotate the motor so that the contacts and
other components are aligned in the neutral position
2.
Confirm that the regulator is in the neutral position.
A. Main movable contacts are located on the neutral
stationary contact, which is located at the 11 o'clock
position and under the reversing switch movable
contact assembly. See Figure 83.
Neutral
Stationary
Contact
Figure 83. Neutral position for main movable contacts.
32
QD5 QUIK-DRIVE TAP-CHANGER INSTALLATION AND MAINTENANCE INSTRUCTIONS MN225012EN March 2016
Figure 84. Neutral position for reversing movable.
Main
Movable
Contacts
Figure 85. Neutral position for position indicator pinion
cam and holding switch.
B. The reversing movable contact is located on the
reversing neutral stationary contact. See Figure 84.
Reversing
Neutral
Stationary
Contact
C. The pinion cam is pointing to the right over the
holding switch actuator. See Figure 85.
Pinion Cam
Reversing
Movable
Contact
Holding Switch
Actuator