3.
Using a 7/16" wrench, loosen and remove both bushing-
mounting bolts. See Figure 56.
Bushing
Mounting
Bolt
Actuator Arm
Figure 56. Reversing actuator arm removed.
4.
Remove the bushing from the reversing actuator shaft.
See Figure 57 .
Reversing
Movable
Contact
Figure 57. Removing reversing movable contact bushing.
24
QD5 QUIK-DRIVE TAP-CHANGER INSTALLATION AND MAINTENANCE INSTRUCTIONS MN225012EN March 2016
Reversing
Movable
Contact
Bushing
Tap-
Changer
Plate
Bushing
5.
Using a small screwdriver (or 5/32" Allen wrench) and
a 1/4" wrench, loosen and remove the self-locking
nuts and reversing logic switch mounting screws. See
Figures 58 and 59.
Reversing Logic
Switch Mounting
Hardware
Figure 58. Logic switch removal.
Reversing
Logic Switch
Figure 59. Reversing logic switch removal.