Implementing The Emergency Stop Function; Cabinet-Installed Multidrives; Multidrive Modules; Implementing The Safe Torque Off Function - ABB ACS880 Series Electrical Planning Instructions

Multidrive cabinets and modules
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

Note:
As standard, the drive contains capacitors connected between the main circuit and the
frame. These capacitors and long motor cables increase the ground leakage current and
may cause fault current circuit breakers to function.

Implementing the Emergency stop function

Cabinet-installed multidrives

You can order the drive with an emergency stop function. For safety reasons, install the
emergency stop devices at each operator control station and at other operating stations
where emergency stop may be needed. See the appropriate emergency stop user's manual
for the wiring, start-up and operation instructions.
Note:
Pressing the stop key
of the drive from position "1" to "0" does not generate an emergency stop of the motor or
separate the drive from dangerous potential.
Option code
User's manual
+Q951
Emergency stop, stop category 0 with opening the main contactor
or breaker with safety relays
+Q952
Emergency stop, stop category 1 with opening the main contactor
or breaker with safety relays
+Q963
Emergency stop, stop category 0 without opening the main con-
tactor or breaker with safety relays
+Q964
Emergency stop, stop category 1 without opening the main con-
tactor or breaker with safety relays
+Q979
Emergency stop, configurable stop category 0 or 1 with FSO-xx
safety functions module

Multidrive modules

For safety reasons, install the emergency stop devices at each operator control station and
at other operating stations where emergency stop may be needed. Implement the emergency
stop according to relevant standards.
You can use the Safe torque off function of the drive (inverter unit) to implement the
Emergency stop function.

Implementing the Safe torque off function

The safe torque off (STO) input is available as standard in all inverter units. See the inverter
unit hardware manual for implementing the Safe torque off function.
on the control panel of the drive, or turning the operating switch
Electrical planning guidelines 35