Implementing A Ground Fault Protecting Function; Cabinet-Installed Multidrives; Residual Current Device Compatibility; Multidrives Modules - ABB ACS880 Series Electrical Planning Instructions

Multidrive cabinets and modules
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

34 Electrical planning guidelines
Option module
Type
Insulation/Isolation
FIO-11
Galvanic isolation between sensor
connector and other connectors (in-
cluding drive control unit connector)
FEN-xx
Galvanic isolation between sensor
connector and other connectors (in-
cluding drive control unit connector)
FAIO-01
Basic insulation between sensor
connector and drive control unit
connector. No insulation between
sensor connector and other I/O
connectors.
Reinforced insulation between
FPTC-
1)
sensor connector and other connect-
xx
ors (including drive control unit con-
nector).
1) Suitable for use in safety functions (SIL2 / PL c rated).

Implementing a ground fault protecting function

Cabinet-installed multidrives

The drive is equipped with an internal ground fault protective function to protect the drive
against ground faults in the motor and motor cable in TN (grounded) networks. This is not
a personnel safety or a fire protection feature. The ground fault protective function can be
disabled with a parameter, refer to the firmware manual.
An optional ground fault monitoring device (+Q953) is available for TN (grounded) systems.
The option includes a ground fault indicator on the drive cabinet door. An optional ground
fault monitoring device (+Q954) is available for IT (ungrounded) systems. The option includes
a ground fault indicator on the drive cabinet door.

Residual current device compatibility

The drive is suitable to be used with residual current devices of Type B.
Note:
As standard, the drive contains capacitors connected between the main circuit and the
frame. These capacitors and long motor cables increase the ground leakage current and
may cause fault current circuit breakers to function.

Multidrives modules

The drive is equipped with an internal ground fault protective function to protect the drive
against ground faults in the motor and motor cable in TN (grounded) networks. This is not
a personnel safety or a fire protection feature. The ground fault protective function can be
disabled with a parameter, refer to the firmware manual.
Residual current device compatibility
The drive is suitable to be used with residual current devices of Type B.
Temperature sensor
type
PTC
KTY
Pt100,
Pt1000
-
x
x
x
x
-
x
x
x
x
-
-
Temperature sensor insulation
requirement
Reinforced insulation
Reinforced insulation
Basic insulation. Connectors of op-
tion module other than sensor con-
nector must be left unconnected.
No special requirement