Availability Of Du/Dt Filter And Common Mode Filter By Drive Type; Additional Requirements For Explosion-Safe (Ex) Motors; And Am; Additional Requirements For Braking Applications - ABB ACS880 Series Electrical Planning Instructions

Multidrive cabinets and modules
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

Availability of du/dt filter and common mode filter by drive type

Inverter frame size
Multidrive cabinets
R1i ... R5i
R6i, R7i
R8i
Multidrive modules
R1i ... R5i
R6i, R7i
R8i
1) 400 V and 500 V single-module units: Option +E205. 690 V units, and units with parallel-connected modules: Standard.
2) For ordering information, see the ACS880-104 inverter modules hardware manual [3AUA0000104271 (English)].

Additional requirements for explosion-safe (EX) motors

If you will use an explosion-safe (EX) motor, follow the rules in the requirements table above.
In addition, consult the motor manufacturer for any further requirements.
Additional requirements for ABB motors of types other than M2_, M3_, M4_, HX_ and
AM_
Use the selection criteria given for non-ABB motors.

Additional requirements for braking applications

When the motor brakes the machinery, the intermediate circuit DC voltage of the drive
increases, the effect being similar to increasing the motor supply voltage by up to 20 percent.
Consider this voltage increase when specifying the motor insulation requirements if the
motor will be braking a large part of its operation time.
Example: Motor insulation requirement for a 400 V AC line voltage application must be
selected as if the drive were supplied with 480 V.
Additional requirements for drives with an IGBT supply unit or regenerative rectifier
unit
It is possible to increase the intermediate circuit DC voltage from the nominal (standard)
level with a parameter in the supply unit control program. If you choose to do this, select
the motor insulation system which withstands the increased DC voltage level.

Additional requirements for ABB high-output and IP23 motors

The rated output power of high output motors is higher than what is stated for the particular
frame size in EN 50347 (2001).
This table shows the requirements for protecting the motor insulation and bearings in drive
systems for ABB random-wound motor series (for example, M3AA, M3AP and M3BP).
du/dt filter
Option +E205
Option +E205
Option +E205 / standard
2)
Add-on kit
2)
Add-on kit
Option +E205 / standard
Electrical planning guidelines 21
Common mode filter (CMF)
Standard
1)
Standard
Add-on kit
1)
Add-on kit
-
-
2)
2)

Advertisement

Table of Contents