Viessmann VITODENS 222-F Installation And Service Instructions Manual page 64

Gas condensing storage combi boiler
Table of Contents

Advertisement

System configuration (parameters)
Heating circuit 1, Heating circuit 2, Heating...
1192.0 "Minimum flow temperature limit, heating circuit 1"
Setting
20 °C
1192.1 "Maximum flow temperature limit, heating circuit 1"
Setting
74 °C
1193.0 "Minimum flow temperature limit, heating circuit 2"
Setting
20 °C
1193.1 "Maximum flow temperature limit, heating circuit 2"
Setting
74 °C
1194.0 "Minimum flow temperature limit, heating circuit 3"
Setting
20 °C
1194.1 "Maximum flow temperature limit, heating circuit 3"
Setting
74 °C
64
(cont.)
Explanations
Minimum flow temperature limit for the heating circuit
20
Minimum limit in the delivered condition 20 °C
1 to 90
Setting range limited by heat generator-specific pa-
rameters
Explanations
Maximum flow temperature limit for the heating circuit
74
Maximum limit in the delivered condition 74 °C
10 to 100
Setting range limited by heat generator-specific pa-
rameters
Explanations
Minimum flow temperature limit for the heating circuit
20
Minimum limit in the delivered condition 20 °C
1 to 90
Setting range limited by heat generator-specific pa-
rameters
Explanations
Maximum flow temperature limit for the heating circuit
74
Maximum limit in the delivered condition 74 °C
10 to 100
Setting range limited by heat generator-specific pa-
rameters
Explanations
Minimum flow temperature limit for the heating circuit
20
Minimum limit in the delivered condition 20 °C
1 to 90
Setting range limited by heat generator-specific pa-
rameters
Explanations
Maximum flow temperature limit for the heating circuit
74
Maximum limit in the delivered condition 74 °C
10 to 100
Setting range limited by heat generator-specific pa-
rameters