Cleaning The Loading Cylinder - Viessmann VITODENS 222-F Installation And Service Instructions Manual

Gas condensing storage combi boiler
Table of Contents

Advertisement

Draining the boiler on the DHW side
Fig. 40

Cleaning the loading cylinder

Note
According to EN 806, a visual inspection and (if neces-
sary) cleaning must be carried out no later than 2
years after commissioning, and as required thereafter.
A
C
B
Commissioning, inspection, maintenance
(cont.)
2. Connect the hose to the drain valve and route it
into a suitable container or drain outlet.
Note
Ensure adequate ventilation in the DHW pipework.
3. Turn the drain valve from lever position
tional) to lever position
Lever position
: The DHW circuit in the appli-
B
ance excluding the DHW cylinder is drained via
the cold water connection.
Lever position
C
: The DHW circuit in the appli-
ance and the DHW cylinder are drained via the
hot water connection.
The cold water connection remains filled.
(opera-
A
or
as required.
B
C
47