Heating circuit 1, Heating circuit 2, Heating...
426.3 "Set flow temperature increased when switching from operation with reduced room temperature to
operation with standard/comfort room temperature, heating circuit 2"
Setting
0 K
426.4 "Duration for set flow temperature increase, heating circuit 2"
Setting
60 min
428.3 "Set flow temperature increased when switching from operation with reduced room temperature to
operation with standard/comfort room temperature, heating circuit 3"
Setting
0 K
428.4 "Duration for set flow temperature increase, heating circuit 3"
Setting
60 min
933.3 "Priority, DHW heating, heating circuit 1"
Setting
OFF
DHW
933.6 "Operating mode, heating circuit 1"
Setting
Weather-compensated without room tem-
perature hook-up
Weather-compensated with room tempera-
ture hook-up
(cont.)
Explanations
Set flow temperature increased when changing from
operation at reduced room temperature to operation at
standard room temperature or comfort room tempera-
ture.
See also chapter "Function description"
0
Delivered condition increase 0 K
0 to 20
Temperature rise adjustable from 0 to 20 K
Explanations
Duration for set flow temperature increase
See also chapter "Function description"
60
Delivered condition 60 min
0 to 120
Temperature rise adjustable from 0 to 120 min
Explanations
Set flow temperature increased when changing from
operation at reduced room temperature to operation at
standard room temperature or comfort room tempera-
ture.
See also chapter "Function description"
0
Delivered condition increase 0 K
0 to 20
Temperature rise adjustable from 0 to 20 K
Explanations
Duration for set flow temperature increase
See also chapter "Function description"
60
Delivered condition 60 min
0 to 120
Temperature rise adjustable from 0 to 120 min
Explanations
Priority of DHW heating over the heating circuit
0
Without DHW heating priority
1
With DHW heating priority
Explanations
Only adjust for systems with one heating circuit. See
also parameter 933.7
Heating mode:
0
Weather-compensated without room temperature in-
fluence
1
Weather-compensated with room temperature influ-
ence
System configuration (parameters)
61