A-3. CL-203-E DCON Command Sets

Command
$AAF
$AAI
$AAM
$AAP
$AAPN
$AA2
$AA5
#AA
#AAN
%AANNTTCCFF
@AAABC
@AAABCN
A-3. CL-203-E DCON Command Sets
Description
read firmware version
read INIT status
response:
!AA0 -> INIT short to GND
!AA1 -> else
read module name
Read Modbus RTU/DCON protocol
response:
!AA0 -> DCON
!AA1 -> Modbus RTU
Set Modbus RTU/DCON protocol
N-> 0: DCON, 1: Modbus RTU
read configuration
read reset status
!AA1 first after power on, !AA0 others
Read All Analog Inputs
response
>(CO in 1 ppm) (CO
0.01%)(temperature in 0.01°C)(temperature in 0.01°F) (dew
point temperature in 0.01°C)(dew point temperature in
0.01°F)
Read Channel Analog Input
N = 0 for CO in 1 ppm, 1 for CO
0.01%, 3 for temperature in 0.01°C, 4 for temperature in 0.01°F, 5
for dew point temperature in 0.01°C, 6 for dew point temperature in
0.01°F
set configuration, NN: new address, TT = 00, CC: new baud rate
FF: data format
Read status of the automatic baseline correction
response
!AAN, N=0: disabled, 1: enabled
Set the automatic baseline correction
N->0: disabled, 1: enabled
in 1 ppm) (relative humidity in
2
in 1 ppm, 2 for relative humidity in
2