A-12. CL-213 / CL-213-E DCON Command Sets
Command
$AAF
$AAI
$AAM
$AAP
$AAPN
$AA2
$AA5
#AA
#AAN
A-12. CL-213 / CL-213-E DCON Command Sets
Description
Reads firmware version, AA is the RS-485 address (hex).
Reads INIT status, AA is the RS-485 address (hex).
response:
!AA0 -> INIT short to GND
!AA1 -> else
Reads module name, AA is the RS-485 address (hex).
Reads Modbus RTU/DCON protocol.
response:
!AA0 -> DCON
!AA1 -> Modbus RTU
Sets Modbus RTU/DCON protocol
N-> 0: DCON, 1: Modbus RTU
Reads configuration, AA is the RS-485 address (hex).
Reads reset status
response
!AA1 first after power on, !AA0 others
Read All Analog Inputs
response
>(CO in 1 ppm) (CO
humidity in 0.01%)(temperature in 0.01°C)(temperature in
0.01°F)
(dew point
temperature in 0.01°F)
Reads Channel Analog Input
N = 0 for CO In 1ppm,
1 for CO
In 1ppm,
2
2 for PM2.5 in 1 ug/m3,
3 for relative humidity in 0.01%,
4 for temperature in 0.01°C,
5 for temperature in 0.01°F,
6 for dew point temperature in 0.01°C,
7 for dew point temperature in 0.01°F
in 1 ppm)(PM2.5 in 1 ug/m3)(relative
2
temperature
in
0.01°C)(dew point
- 148 -