Raised-Floor Lateral Stability Ratings; Raised-Floor Panel Ratings; Figure 4-3. Vsm5-Vtss Cabinet Weight Distribution And Leveler Locations; Table 4-5. Raised Flooring Horizontal Force Chart - Sun Microsystems StorageTek 96257 System Planning Manual

Planning and system assurance guide virtual tape storage system
Table of Contents

Advertisement

Site Readiness Planning

Figure 4-3. VSM5-VTSS Cabinet Weight Distribution and Leveler Locations

47.11
(18.55)
(2X)
6.29 (2.725)
(2X)
6.29
(2.725)
(2X)

Raised-Floor Lateral Stability Ratings

In areas of high earthquake activity, the lateral stability of raised floors must be consid-
ered. Raised floors where VSM5 system equipment is installed must be able to resist the
horizontal-stress levels shown in

Table 4-5. Raised Flooring Horizontal Force Chart

Seismic Risk Zone
1
2A
2B
3
4
Note: Note: Horizontal forces are based on the 1991 Uniform Building Code (UBC) Sections 2336 and 2337, and
assume minimum operating clearances for multiple VSM5 cabinets. Installations in areas not covered by the
UBC should be engineered to meet seismic code provisions of the local jurisdiction.

Raised-Floor Panel Ratings

Raised floor panels must be able to resist a concentrated load of 454 kg (1000 lbs.) and a
rolling load of 181 kg (400 lbs.) anywhere on the panel with a maximum deflection of 2 mm
(0.08 in.). Perforated floor panels are not required for VSM5 system equipment, but if used
must comply with the same ratings.
4-54
92.1 (36.26
97.40
(261)
X
109.72
(294)
77.59 (30.55)
(2X)
Table
Horizontal Force (V) Applied at Top of Pedestal
Sun Confidential: Internal Only
Revision A
)
75.01
Z
(201)
X
84.34
(226)
Z
4-5.
13.5 kg / 29.7 lbs
20.2 kg / 44.6 lbs
26.9 kg / 59.4 lbs
40.4 kg / 89.1 lbs
53.9 kg / 118.8 lbs
77.1
(30.35)
14.98
(5.90)
(2X)
A504 026
96257