Application Manual

IRF

The IRF contact functions as an output contact for the self-supervision system of the
protection relay. Under normal operating conditions, the protection relay is energized
and the contact is closed (X100:3-5). When a fault is detected by the self-supervision
system or the auxiliary voltage is disconnected, the contact X100:3-5 drops off and the
contact X100:3-4 closes.
Table 33:
IRF contact
Terminal
X100:3
X100:4
X100:5
Protection relay's physical connections
Description
IRF, common
Closed; IRF, or U
Closed; no IRF, and U
Section 5
disconnected
aux
connected
aux
71