6.4.3.3 Second priority cut-off
The Auxiliary Contact can use to cut-off second priority load with the criteria of the battery status or
overtemp. One of the 4 LED 15 to 18 or 10 will be chosen as the cut off criteria. The second prior-
ity loads will be supply only if the battery as a sufficient residual capacity

6.5 Disabling some of the XP-COMPACT functions

Each different function charger, inverter and transfer can be disabled. This is useful for specific
applications witch required to disable some of these tree functions.
If you press the button (20) more than 2 seconds, you can have the access to the different possi-
bilities shown in the following diagram.
In programming mode the display show only the different types of program with the three DEL 2,7
and 9 to each functions. To change the type of programming press shortly the button 20 until your
reach to the right function use according table below. After 10 seconds the XP-COMPACT exits the
programming mode and load the new change.
In user mode, the disabled functions are displayed by blinking LED. So you can see in witch mode
is disabled.
6.5.1

Diagram of the different mode

1
AC IN
CHARGER
2
1
AC IN
CHARGER
2
1
AC IN
2
CHARGER
1
AC IN
CHARGER
2

7 Maintenance

Apart from the periodic controls mentioned for the connections, the XP-COMPACT does not need
any maintenance. Keep the appliance clean and from time to time wipe it clean with a damp cloth.

8 EC Compliance

Hereby we state that the products described in this user manual meet the following standards:
EN50081 I/II, EN55014 – EN61000-2-3, IEC801 II/III/IV, LVD 73/23/EEC, EMC Dir. 89/336
st
CH-1950 Sion the 1
User manual
9
8
AC OUT
7
9
INVERTER
8
AC OUT
7
9
INVERTER
8
AC OUT
7
9
INVERTER
8
AC OUT
7
9
INVERTER
of January 2003
XP-COMPACT V2.0 E
Show an off LED
Show a blinking LED
Show a lighted LED
All the functions are enabled. This is the fac-
tory setting.
The inverter is disabled. Only the transfer
switch and the charger will work normally.
Charger and transfer switch are disabled. the
inverter will work continuously even if there is
a correct AC voltage at the input
Inverter and charger are both disabled.
Only the transfer switch function is enabled in
input voltage and frequency is OK.
STUDER INNOTEC (R.Studer)