Section 5
630 series
Communication Protocol Manual
Supported services
IEC 61850-7-2 describes the services in the standard. IEC 61850-8-1 describes how
the services are applied in the communication. The conformance documents contain
the description of the supported services in the IED.
Services that are not mentioned in this chapter or in the conformance document are not
supported.
Data set
Define data sets by the SCD description.
Create data sets under LD0/LLN0.
Substitution
Substitution is supported for the respective DATA, according to IEC 61850-7-4, that
have the substitution attributes defined.
Note that SubID and SubQ are not used.
Setting group control block
Change of setting group is supported, that is the actSG attribute. This attribute is not
one of the explicit definitions in SCL, but a consequence of the defined setting group
control block according to IEC 61850-6.
There is only one setting group control block, which is located in LD0/LLN0 (Logical
Device/Logical Node 0).
Change or edit of setting values as well as reading of setting values is neither
supported nor visible in IEC 61850.
Note that the actual number of used setting groups is defined by the
parameter MaxNoSetGRP in the function SETGRPS, which is
configured in PST in PCM600.
Report control block
For properties about report control blocks, see PIXIT.
UnBuffered reporting as well as Buffered reporting is supported.
Section 5
Supported services
27