Time Undercurrent Ptuc; St - T_Ena_Close; Inhrec V1_Dsps Stval St - Blk_Close; St Blk_Close - ABB Relion 630 Series Communication Protocol Manual

Iec 61850 communication protocol
Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

Section 7
Logical node data model
DO name
DO type
TmmRecEna
v1_dINS
RsTmp
v1_dSPC
InhRec
v1_dSPS
SenFlt
v1_dSPS
TmpUsed
v2_dMV
7.4.20
154
DA name
FC
q
ST
t
ST
Oper.ctlVal
CO
Oper.origin.orCat
CO
Oper.origin.orIdent
CO
Oper.ctlNum
CO
Oper.T
CO
Oper.Test
CO
Oper.Check
CO
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
mag.f
MX
q
MX
t
MX

Time undercurrent PTUC

LN type
LOFLPTUC (revision 0) LOFL
T
Signal
-
T_ENA_CLOSE
-
T_ENA_CLOSE
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
BLK_CLOSE
-
BLK_CLOSE
-
BLK_CLOSE
-
-
-
-
-
-
-
TEMP_AMB
-
TEMP_AMB
-
TEMP_AMB
LN prefix LN class Function block name
PTUC
LOFLPTUC
1MRS756793 E
Mon/C
Description
md
Mon
Quality: Estimated time to reset of
block reclose
Mon
Timestamp: Estimated time to
reset of block reclose
Cmd
Command parameter for
IEC61850
Cmd
Command parameter for
IEC61850
Cmd
Command parameter for
IEC61850
Cmd
Command parameter for
IEC61850
Cmd
Command parameter for
IEC61850
Cmd
Command parameter for
IEC61850
Cmd
Command parameter for
IEC61850
Mon
Thermal overload indicator. To
inhibit reclose
Mon
Quality: Thermal overload
indicator. To inhibit reclose
Mon
Timestamp: Thermal overload
indicator. To inhibit reclose
Mon
Error signal from the temperature
sensor
Mon
Quality: Error signal from the
temperature sensor
Mon
Timestamp: Error signal from the
temperature sensor
Mon
Ambient temperature used in the
calculations
Mon
Quality: Ambient temperature
used in the calculations
Mon
Timestamp: Ambient temperature
used in the calculations
Communication Protocol Manual
630 series