Section 7
Logical node data model
DO name
DO type
FltZ
c_dCMV
Mod
c_dINC
FltDiskm
c_dMV
FltLoop
e_dINS
FltDisVald
v1_dINS
FltAlm
v1_dSPS
TrgSt
v1_dSPS
FltLoopR
v2_dMV
FltLoopX
v2_dMV
Table continues on next page
202
DA name
FC
t
MX
stVal
ST
q
ST
t
ST
mag.f
MX
q
MX
t
MX
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
mag.f
MX
q
MX
t
MX
mag.f
MX
q
MX
T
Signal
-
RF
-
-
-
-
-
-
-
FLT_DISTANCE
-
FLT_DISTANCE
-
FLT_DISTANCE
-
FAULT_LOOP
-
FAULT_LOOP
-
FAULT_LOOP
-
EF_VALIDITY
-
EF_VALIDITY
-
EF_VALIDITY
-
ALARM
-
ALARM
-
ALARM
-
TRIGG_OUT
-
TRIGG_OUT
-
TRIGG_OUT
-
RFLOOP
-
RFLOOP
-
RFLOOP
-
XFLOOP
-
XFLOOP
1MRS756793 E
Mon/C
Description
md
Mon
Timestamp: Fault resistance in
primary ohms
Mon
Mode status parameter for 61850
Mon
Quality: Mode status parameter for
61850
Mon
Timestamp: Mode status
parameter for 61850
Mon
Fault distance in units selected by
the user (pu)
Mon
Quality: Fault distance in units
selected by the user (pu)
Mon
Timestamp: Fault distance in units
selected by the user (pu)
Mon
Fault impedance loop used for
distance measurement
Mon
Quality: Fault impedance loop
used for distance measurement
Mon
Timestamp: Fault impedance loop
used for distance measurement
Mon
Validity of earth fault location
Mon
Quality: Validity of earth fault
location
Mon
Timestamp: Validity of earth fault
location
Mon
Alarm signal indicating that fault is
located between set limits
Mon
Quality: Alarm signal indicating
that fault is located between set
limits
Mon
Timestamp: Alarm signal
indicating that fault is located
between set limits
Mon
Signal indicating function
triggering
Mon
Quality: Signal indicating function
triggering
Mon
Timestamp: Signal indicating
function triggering
Mon
Fault loop resistance in primary
ohms
Mon
Quality: Fault loop resistance in
primary ohms
Mon
Timestamp: Fault loop resistance
in primary ohms
Mon
Fault loop reactance in primary
ohms
Mon
Quality: Fault loop reactance in
primary ohms
Communication Protocol Manual