ABB Relion 630 Series Communication Protocol Manual page 272

Iec 61850 communication protocol
Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

Section 7
Logical node data model
DO name
DO type
RsSprChaTm
v1_dSPC
OpnAlm
v1_dSPS
ClsAlm
v1_dSPS
OpNumAlm
v1_dSPS
OpNumLO
v1_dSPS
APwrAlm
v1_dSPS
APwrLO
v1_dSPS
Table continues on next page
266
DA name
FC
Oper.origin.orCat
CO
Oper.origin.orIdent
CO
Oper.ctlNum
CO
Oper.T
CO
Oper.Test
CO
Oper.Check
CO
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
T
Signal
-
-
-
-
-
-
-
-
-
-
-
-
-
TRV_T_OP_ALM
-
TRV_T_OP_ALM
-
TRV_T_OP_ALM
-
TRV_T_CL_ALM
-
TRV_T_CL_ALM
-
TRV_T_CL_ALM
-
OPR_ALM
-
OPR_ALM
-
OPR_ALM
-
OPR_LO
-
OPR_LO
-
OPR_LO
-
IPOW_ALM
-
IPOW_ALM
-
IPOW_ALM
-
IPOW_LO
-
IPOW_LO
-
IPOW_LO
1MRS756793 E
Mon/C
Description
md
Cmd
Command parameter for
IEC61850
Cmd
Command parameter for
IEC61850
Cmd
Command parameter for
IEC61850
Cmd
Command parameter for
IEC61850
Cmd
Command parameter for
IEC61850
Cmd
Command parameter for
IEC61850
Mon
CB open travel time exceeded set
value
Mon
Quality: CB open travel time
exceeded set value
Mon
Timestamp: CB open travel time
exceeded set value
Mon
CB close travel time exceeded set
value
Mon
Quality: CB close travel time
exceeded set value
Mon
Timestamp: CB close travel time
exceeded set value
Mon
Number of CB operations exceeds
alarm limit
Mon
Quality: Number of CB operations
exceeds alarm limit
Mon
Timestamp: Number of CB
operations exceeds alarm limit
Mon
Number of CB operations exceeds
lockout limit
Mon
Quality: Number of CB operations
exceeds lockout limit
Mon
Timestamp: Number of CB
operations exceeds lockout limit
Mon
Accumulated currents power
(Iyt),exceeded alarm limit
Mon
Quality: Accumulated currents
power (Iyt),exceeded alarm limit
Mon
Timestamp: Accumulated currents
power (Iyt),exceeded alarm limit
Mon
Accumulated currents power
(Iyt),exceeded lockout limit
Mon
Quality: Accumulated currents
power (Iyt),exceeded lockout limit
Mon
Timestamp: Accumulated currents
power (Iyt),exceeded lockout limit
Communication Protocol Manual