ABB Relion 630 Series Communication Protocol Manual page 132

Iec 61850 communication protocol
Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

Section 7
Logical node data model
DO name
DO type
AngScyBC
v2_dMV
AngScyCA
v2_dMV
AngPriScyA
v2_dMV
AngPriScyB
v2_dMV
AngPriScyC
v2_dMV
Table 80:
TR2PTDF Logical node data (instance 2)
DO name
DO type
Str
a_dACD
Table continues on next page
126
DA name
FC
mag.f
MX
q
MX
t
MX
mag.f
MX
q
MX
t
MX
mag.f
MX
q
MX
t
MX
mag.f
MX
q
MX
t
MX
mag.f
MX
q
MX
t
MX
DA name
FC
general
ST
phsA
ST
phsB
ST
phsC
ST
q
ST
T
Signal
-
I_ANGL_B2_C2
-
I_ANGL_B2_C2
-
I_ANGL_B2_C2
-
I_ANGL_C2_A2
-
I_ANGL_C2_A2
-
I_ANGL_C2_A2
-
I_ANGL_A1_A2
-
I_ANGL_A1_A2
-
I_ANGL_A1_A2
-
I_ANGL_B1_B2
-
I_ANGL_B1_B2
-
I_ANGL_B1_B2
-
I_ANGL_C1_C2
-
I_ANGL_C1_C2
-
I_ANGL_C1_C2
T
Signal
-
-
-
-
-
-
-
-
-
-
1MRS756793 E
Mon/C
Description
md
Mon
Current phase angle phase B –
phase C, winding 2
Mon
Quality: Current phase angle
phase B – phase C, winding 2
Mon
Timestamp: Current phase angle
phase B – phase C, winding 2
Mon
Current phase angle phase C –
phase A, winding 2
Mon
Quality: Current phase angle
phase C – phase A, winding 2
Mon
Timestamp: Current phase angle
phase C – phase A, winding 2
Mon
Current phase angle diff between
winding 1 and 2, phase A
Mon
Quality: Current phase angle diff
between winding 1 and 2, phase A
Mon
Timestamp: Current phase angle
diff between winding 1 and 2,
phase A
Mon
Current phase angle diff between
winding 1 and 2, phase B
Mon
Quality: Current phase angle diff
between winding 1 and 2, phase B
Mon
Timestamp: Current phase angle
diff between winding 1 and 2,
phase B
Mon
Current phase angle diff between
winding 1 and 2, phase C
Mon
Quality: Current phase angle diff
between winding 1 and 2, phase C
Mon
Timestamp: Current phase angle
diff between winding 1 and 2,
phase C
Mon/C
Description
md
Mon
5th harmonic restraint blocking for
PHAR LN, combined
Mon
5th harmonic restraint blocking for
PHAR LN, phase A
Mon
5th harmonic restraint blocking for
PHAR LN, phase B
Mon
5th harmonic restraint blocking for
PHAR LN, phase C
Mon
Quality: 5th harmonic restraint
blocking for PHAR LN, combined
Communication Protocol Manual
630 series

Advertisement

Table of Contents
loading

Table of Contents