Installation, connecting up, commissioning
5.1 Important notes on using the device
Power supply
The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a
Limited Power Source (LPS).
This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1
must be connected to the power supply terminals. The power supply unit for the equipment
power supply must comply with NEC Class 2, as described by the National Electrical Code
(r) (ANSI / NFPA 70).
EXPLOSION HAZARD
DO NOT CONNECT OR DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR
COMBUSTIBLE ATMOSPHERE IS PRESENT.
EXPLOSION HAZARD
SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION
2 OR ZONE 2.
When used in hazardous environments corresponding to Class I, Division 2 or Class I,
Zone 2, the device must be installed in a cabinet or a suitable enclosure.
5.1.2

Notices on use in hazardous areas according to ATEX / IECEx

Requirements for the cabinet
To comply with EC Directive 94/9 (ATEX95) or the conditions of IECEx, this enclosure or
cabinet must meet the requirements of at least IP54 in compliance with EN 60529.
32
WARNING
WARNING
WARNING
WARNING
WARNING
CP 443-1 RNA
Manual, 03/2019, C79000-G8976-C299-04