See MM8000 MP4.81 Release Notes (Doc. # A6V10062509) for PX models and quantity supported
Building Technologies
CPS Fire Safety
Subsystems that can be connected in this way
Type
Name
Fire panel
FS20 Sinteso
Fire panel
FS720
Cerberus PRO
Fire panel
STT20
Building
DESIGO PX
automation
Additional components required for the various management station types
Type
Additional
components
Foreign station
OPC client head end
OPC Server
BACnet Driver
MM8000
BACnet Driver
Limits and restrictions
Type
Version
MM8000
MP4.81
MK8000
MP4.81
049_DMS_DMS8000_Application_Specification_Planning_MP4.81_A6V10063710_a_en.doc
MM8000
Name
Any OPC DA/UA
compliant client
MK8000
NS8011
NS8011
Restrictions
Up to 64 BACnet devices (FCxx/FTxx and/or
DESIGO PX) per Server/FEP stations can be
connected.
Note: Panels from an FS20 system (or project)
cannot be split to communicate to 2 separate
FEPs (2 BACnet clients).
FS20 Sinteso/FS720 Cerberus PRO Systems:
Limit 16 FCxx/FTxx per SAFEDLINK loop
Limit 64 FCxx/FTxx on multiple SAFEDLINK
loops
Max. 2 GAP stations in FCnet/SAFEDLINK
topology
Max. 2 BACnet clients
STT20 in FCnet/SAFEDLINK:
1 FCnet/SAFEDLINK network with
- max. 10 STT20 (FCGW20-02) and
- max. 12 FC20xx panels
DESIGO PX displays events to indicate when
conditions are abnormal – no additional informa-
tion regarding an event such as causes or condi-
tions is available on the management station.
DESIGO PX not supported.
Automation level configurations
Supported by
MK8000
MP4.81
MP4.81
X
X
X
X
X
X
X
Version
OPC DA2.0x
OPC UA 1.02
MP4.81
MP4.81
MP4.81
41
09.2016