Installation In The Vicinity Of Pumps; Ground; General Information On Ground Connections; Metal Pipe With Fixed Flanges - ABB FSM4000 Series Commissioning Instruction

Hide thumbs Also See for FSM4000 Series:
Table of Contents

Advertisement

3.6.7

Installation in the vicinity of pumps

For flowmeter primaries that are installed near pumps or other
vibration-causing fixtures, the use of mechanical vibration control
components is mandatory.
Change from one to two columns
3.7

Ground

3.7.1

General information on ground connections

Observe the following items when grounding the device:
Use the supplied green-yellow cable as a ground wire.
Connect the ground screw for the flowmeter sensor (on flange and transmitter housing) to
the station ground.
The connection box must also be grounded.
For plastic pipes or pipes with insulating lining, the ground is provided by the grounding plate
or grounding electrodes.
When stray potentials are present, install a grounding plate at the front and back of the
flowmeter sensor.
For measurement-related reasons, the potentials in the station ground and in the pipeline
should be identical.
An additional ground via the terminals is not required.
Important
If the flowmeter sensor is installed in plastic or earthenware pipelines, or in pipelines with an
insulating lining, transient current may flow through the grounding electrode in special cases.
In the long term, this may destroy the flowmeter sensor, since the ground electrode will in turn
degrade electrochemically. In these special cases, the connection to the ground must be
performed using grounding plates.
3.7.2

Metal pipe with fixed flanges

Fig. 16
D184B141U02
1
2
Flange design
FSM4000
Fig. 15
Wafer design
Installation
G00207
G00530
EN - 15