Download Print this page

Rack Enclosure Requirements - Sun Microsystems Sun Enterprise 220R Setup And Rackmounting Manual

Hide thumbs Also See for Sun Enterprise 220R:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
A
A P P E N D I X

Rack Enclosure Requirements

The server is designed so that you can install it into a Sun 72-inch (184-cm) tall
Sun expansion cabinet or other EIA-compliant industry-standard rack enclosure
that meets the requirements listed in the table below. You need a Sun
rackmounting kit for each server that you will rackmount.
Rack Enclosure Feature
Load Bearing Capacity
Vertical Space
Requirements
Airflow
Requirement
The rack must firmly support the weight of a Sun Enterprise 220R
server (75 lbs, 34 kg), plus the weight of the rackmounting
hardware, plus the weight of any other installed devices.
Each server requires four rack units (7 inches, 17.78 cm) of
vertical space for rack installation. A 72-inch (183-cm) cabinet
can hold up to nine servers.
The system requires 113 cfm at 40
This air-flow rate corresponds to 328 lb/hr at any
altitude and to 78 cfm at 40
For proper ventilation, each system in the rack enclosure requires
28 square inches (181 square cm) of unrestricted airflow into the
front of the system, and 23 square inches (148 square cm) of
unrestricted exhaust port at the back of the system. Maintain a
minimum 1.5 inches (3.8 cm) clearance between the system and
any front or back doors.
o
C and 10,000 feet.
o
C and sea level.
en-35

Advertisement

loading

This manual is also suitable for:

Enterprise 420r