3. Turn on the appliance at the ON/OFF key on the
display.
4. Press the ON/OFF and "M" Menu keys at the same
time to access the TECHNICAL MENU.
5. Use the TOUCH PAD to select the installer menu
.
Press the Enter key to confirm
Select the "V" symbol and confirm
The message V1 flashes;
Perform the setting of the fan V1;
access the menu by pressing enter, the display
shows:
V V
V V
Press the Enter key to confirm
Change the voltage value relative to the fan speed
using the TOUCH PAD
pressure gauge displays a value equal to the value
of the objective pressure drop (Pascal) shown on
the display.
V1 fan
speed voltage
80 = 8.0 Volt
V V
Objective
fan rpm
pressure drop
Press the Enter key to confirm
Before going on to set the fan V2, you must dis-
connect the differential pressure gauge from
connections P3 and P4 and put the rubber caps
back in place.
English
.
.
set the nominal de-
sign flow rate (m
3
using the TOUCH
+
PAD
.
_
.
+
until the differential
_
=
.
/h)
31